6ES7215-1AG31-0XB0 CPU 1215C, DC/DC/DC, 14DI/10DO/2AI/2AO

Product Code: 6ES7215-1AG31-0XB0

Availability: In Stock

Price: $420.36
Artikelnummer 6ES7215-1AG31-0XB0
SIMATIC S7-1200, CPU 1215C, COMPACT CPU, DC/DC/DC, 2 PROFINET PORT, ONBOARD I/O: 14 DI 24V DC; 10 DO 24V DC 0.5A 2 AI 0-10V DC, 2 AO 0-20MA DC, POWER SUPPLY: DC 20.4 - 28.8 V DC, PROGRAM/DATA MEMORY: 100 KB
General information
Engineering with
● Programming package STEP 7 V11 SP2 or higher
Display
with display No
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 5 V
● permissible range, upper limit (DC) 250 V
Input current
Current consumption (rated value) 500 mA; Typical
Current consumption, max. 1 500 A; 24 V DC
Inrush current, max. 12 A; at 28.8 V DC
Output current
Current output to backplane bus (DC 5 V), max. 1 600 mA; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Type of memory EEPROM
Usable memory for user data 100 kbyte
Work memory
● Integrated 100 kbyte
● expandable No
Load memory
● Integrated 4 Mbyte
Backup
● present Yes; maintenance-free
● without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs; / instruction
for word operations, typ. 1.7 µs; / instruction
for floating point arithmetic, typ. 2.5 µs; / instruction
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 10 kbyte
Flag
● Number, max. 8 kbyte; Size of bit memory address area
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
● Hardware clock (real-time clock) Yes
● Deviation per day, max. +/- 60 s/month at 25 °C
● Backup time 480 h; Typical
Digital inputs
Number of digital inputs 14; Integrated
● of which, inputs usable for technological functions 6; HSC (High Speed Counting)
integrated channels (DI) 14
m/p-reading Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 14
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 VDC at 2.5 mA
Input current
● for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable Yes; 0.2 ms, 0.4 ms, 0.8 ms, 1.6 ms, 3.2 ms, 6.4 ms and 12.8 ms, selectable in groups of four
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— Parameterizable Yes
for counter/technological functions
— Parameterizable Yes; Single phase : 3 at 100 kHz & 3 at 30 kHz, differential: 3 at 80 kHz & 3 at 30 kHz
Cable length
● Cable length, shielded, max. 500 m; 50 m for technological functions
● Cable length unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 10
● of which high-speed outputs 4; 100 kHz Pulse Train Output
integrated channels (DO) 10
short-circuit protection No; to be provided externally
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Output voltage
● for signal "0", max. 0.1 V; with 10 kOhm load
● for signal "1", min. 20 V
Output current
● for signal "1" rated value 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", max. 1 µs
● "1" to "0", max. 5 µs
Switching frequency
● of the pulse outputs, with resistive load, max. 100 kHz
Relay outputs
● Max. number of relay outputs, integrated 0
Cable length
● Cable length, shielded, max. 500 m
● Cable length unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Integrated channels (AI) 2; 0 to 10 V
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● Cable length, shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 2
Integrated channels (AO) 2
Cable length
● Cable length, shielded, max. 100 m; Shielded, twisted wire pair
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Encoder
Connectable encoders
● 2-wire sensor Yes
1st interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
Automatic detection of transmission speed Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
● PROFINET IO Controller Yes
2nd interface
Interface type PROFINET
Physics Ethernet
Communication functions
S7 communication
● supported Yes
● as server Yes
● As client Yes
Open IE communication
● TCP/IP Yes
● ISO-on-TCP (RFC1006) Yes
● UDP Yes
Web server
● supported Yes
● User-defined websites Yes
Number of connections
● overall 16; dynamically
Test commissioning functions
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 100 kHz
Frequency meter Yes
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Galvanic isolation
Galvanic isolation digital inputs
● Galvanic isolation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Galvanic isolation digital outputs
● Galvanic isolation digital outputs Yes
● between the channels No
● between the channels, in groups of 1
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes
● Interference immunity on signal lines acc. to IEC 61000-4-4 Yes
Surge immunity
● on the supply lines acc. to IEC 61000-4-5 Yes
Immunity against conducted interference induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
Degree of protection to EN 60529
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
UL approval Yes
cULus Yes
RCM (formerly C-TICK) Yes
FM approval Yes
Marine approval
● Marine approval Yes
Ambient conditions
Operating temperature
● Min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Storage/transport temperature
● Min. -40 °C
● max. 70 °C
Air pressure
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Vibrations 2G wall mounting, 1G DIN rail
● Operation, checked according to IEC 60068-2-6 Yes
Shock test
● checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27 half-sine: strength of the shock 15 g (peak value), duration 11 ms
Climatic and mechanical conditions for storage and transport
Climatic conditions for storage and transport
Free fall
— Drop height, max. (in packaging) 0.3 m; five times, in dispatch package
Temperature
— Permissible temperature range -40 °C to +70 °C
Relative humidity
— Permissible range (without condensation) at 25 °C 95 %
Mechanical and climatic conditions during operation
Climatic conditions in operation
Temperature
— Min. -20 °C
— max. 60 °C
Air pressure acc. to IEC 60068-2-13
— Permissible air pressure 1080 to 795 hPa
— Permissible operating height -1000 to 2000 m
Pollutant concentrations
— SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● can be set Yes
Dimensions
Width 130 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 520 g
last modified: 13.10.2014