6GK7443-5DX03-0XE0 COMMUNICATION PROCESSOR CP 443-5 EXT

Product Code: 6GK7443-5DX03-0XE0

Availability: In Stock

Price: $732.95
Artikelnummer 6GK7443-5DX03-0XE0
Product type designation CP 443-5 Extended
SIMATIC NET, CP 443-5 EXTENDED COMMUNICATIONS PROCESSOR FOR CONNECTING SIMATIC S7-400 TO PROFIBUS, DP, S5-COMPATIBLE PG/OP AND S7 COMMUNICATION
Transmission rate
Transfer rate
● at the 1st interface / acc. to PROFIBUS 9.6 kbit/s ... 12 Mbit/s
Interfaces
Number of interfaces / acc. to Industrial Ethernet 0
Number of electrical connections
● at the 1st interface / acc. to PROFIBUS 1
Design of the electrical connection
● at the 1st interface / acc. to PROFIBUS 9-pin Sub-D socket (RS485)
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltage DC
Supply voltage / 1 / from backplane bus 5 V
Supply voltage 5 V
Relative symmetrical tolerance / for DC
● at 5 V 5 %
Relative positive tolerance / for DC / at 24 V 5 %
Relative negative tolerance / for DC / at 24 V 5 %
Consumed current
● from backplane bus / for DC / at 5 V / typical 1.3 A
Active power loss 6.5 W
Permitted ambient conditions
Ambient temperature
● during operation 0 ... 60 °C
● during storage -40 ... +70 °C
● during transport -40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum 95 %
Protection class IP IP20
Design, dimensions and weight
Module format Compact module S7-400 single width
Width 25 mm
Height 290 mm
Depth 210 mm
Net weight 0.8 kg
Product properties, functions, components / general
Number of units
● per CPU / maximum 14
● Note depending on CPU type
Performance data
Performance data / open communication
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks
● maximum 16
Amount of data
● as user data per connection / for open communication / by means of SEND/RECEIVE blocks / maximum 240 byte
Performance data / PROFIBUS DP
Service / as DP master
● DPV1 Yes
Number of DP slaves / on DP master / usable 125
Amount of data
● of the address area of the inputs / as DP master / total 4096 byte
● of the address area of the outputs / as DP master / total 4096 byte
● of the address area of the inputs / per DP slave 244 byte
● of the address area of the outputs / per DP slave 244 byte
Performance data / S7 communication
Number of possible connections / for S7 communication
● maximum 48
Performance data / telecontrol
Protocol / is supported
● TCP/IP No
Product functions / management, configuration
Configuration software
● required STEP 7 V5.4 SP4 or higher and NCM S7 for PROFIBUS
Further Information / Internet Links
Internet-Link
● to website: Selector SIMATIC NET SELECTION TOOL http://www.siemens.com/snst
● to website: Industrial communication http://www.siemens.com/simatic-net
● to website: Information and Download Center http://www.siemens.com/automation/net/catalog
● to website: Image database http://automation.siemens.com/bilddb
● to website: CAx Download Manager http://www.siemens.com/cax
● to website: Industry Online Support http://support.automation.siemens.com
last modified: 03.11.2014
Date
05.11.2014
Changes preserved
© Copyright Siemens AG 2014