Product type designation |
CP 343-1 Advanced |
|
SIMATIC NET, CP 343-1 ADVANCED COMMUNICATION PROCESSOR FOR CONNECTING SIMATIC S7-300 TO IND. ETHERNET VIA PROFINET-IO CONTROLLER, PROFINET CBA,ISO, TCP/IP AND UDP, S7-KOMM., FETCH/WRITE, SEND/RECEIVE, WITH AND W/O RFC1006, HTTP W JAVA, MULTICAST, LOAD. COMM. BLOCKS, HTML DIAGN.,FTP CLIENT/SERVER E-MAIL, SNMP, DHCP, NTP-CPU SYNC, 10/100 MBIT, ONLY RJ45 PORT |
Transmission rate |
Transfer rate |
|
● at the 1st interface |
10 ... 100 Mbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet |
1 |
Number of electrical connections |
|
● at the 1st interface / acc. to Industrial Ethernet |
1 |
● for power supply |
1 |
Design of the electrical connection |
|
● at the 1st interface / acc. to Industrial Ethernet |
RJ45 port |
● for power supply |
2-pole plugable terminal block |
design of the removable storage / C-PLUG |
Yes |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage |
DC |
Supply voltage / 1 / from backplane bus |
5 V |
Supply voltage |
24 V |
Supply voltage / external |
24 V |
Relative positive tolerance / for DC / at 24 V |
20 % |
Relative negative tolerance / for DC / at 24 V |
15 % |
Consumed current |
|
● from backplane bus / for DC / at 5 V / typical |
0.14 A |
Active power loss |
14.7 W |
Permitted ambient conditions |
Ambient temperature |
|
● for vertical installation / during operation |
0 ... 40 °C |
● for horizontally arranged busbars / during operation |
0 ... 60 °C |
● during storage |
-40 ... +70 °C |
● during transport |
-40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum |
95 % |
Protection class IP |
IP20 |
Design, dimensions and weight |
Module format |
Compact module S7-300 double width |
Width |
80 mm |
Height |
125 mm |
Depth |
120 mm |
Net weight |
0.8 kg |
Mounting type |
|
● S7-300 rail mounting |
Yes |
Performance data |
Performance data / open communication |
Number of possible connections / for open communication / by means of SEND/RECEIVE blocks |
|
● maximum |
16 |
Amount of data |
|
● as user data per ISO connection / for open communication / by means of SEND/RECEIVE blocks / maximum |
8 Kibyte |
● as user data per ISO on TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum |
8 Kibyte |
● as user data per TCP connection / for open communication / by means of SEND/RECEIVE blocks / maximum |
8 Kibyte |
● as user data per UDP connection / for open IE communication / by means of SEND/RECEIVE blocks / maximum |
2 Kibyte |
Number of Multicast stations |
16 |
Performance data / S7 communication |
Number of possible connections / for S7 communication |
|
● maximum |
16 |
Performance data / multi-protocol mode |
Number of active connections / with multi-protocol mode |
48 |
Performance data / IT functions |
Number of possible connections |
|
● as client / by means of FTP / maximum |
10 |
● as server / by means of FTP / maximum |
2 |
● as server / by means of HTTP / maximum |
4 |
● as e-mail client / maximum |
1 |
Amount of data / as user data for email / maximum |
8 Kibyte |
Storage capacity / of the user memory |
|
● as flash memory file system |
28 Mibyte |
● as RAM |
30 Mibyte |
Number of possible write cycles / of the flash memory cells |
100000 |
Performance data / PROFINET communication / as PN IO-Controller |
Number of PN IO devices / on PROFINET IO controller / usable / total |
125 |
Number of external PN IO lines / with PROFINET / per rack |
1 |
Amount of data |
|
● as user data for input variables / as PROFINET IO controller / maximum |
4 Kibyte |
● as user data for input variables / as PROFINET IO controller / maximum |
4 Kibyte |
● as user data for input variables per PN IO device / as PROFINET IO controller / maximum |
1433 byte |
● as user data for output variables per PN IO device / as PROFINET IO controller / maximum |
1433 byte |
Performance data / PROFINET CBA |
Number of remote connection partners / with PROFINET CBA |
64 |
Number of connections / with PROFINET CBA / total |
1000 |
Amount of data |
|
● as user data for digital inputs / with PROFINET CBA / maximum |
8 Kibyte |
● as user data for digital outputs / with PROFINET CBA / maximum |
8 Kibyte |
● as user data for arrays and data types / in the case of acyclic transmission / with PROFINET CBA / maximum |
8 Kibyte |
● as user data for arrays and data types / with PROFINET CBA / with cyclical transfer / maximum |
450 byte |
● as user data for arrays and data types / with PROFINET CBA / in the case of local interconnection / maximum |
2400 byte |
Performance data / PROFINET CBA / remote connection / with acyclic transmission |
Refresh time / of the remote interconnections / in the case of acyclic transmission / with PROFINET CBA |
100 ms |
|
|
● Number of remote connections to input variables / in the case of acyclic transmission / with PROFINET CBA / maximum |
128 |
● Number of remote connections to output variables / in the case of acyclic transmission / with PROFINET CBA / maximum |
128 |
Amount of data |
|
● as user data for remote interconnections with input variables / in the case of acyclic transmission / with PROFINET CBA |
8 Kibyte |
● as user data for remote interconnections with output variables / in the case of acyclic transmission / with PROFINET CBA |
8 Kibyte |
Performance data / PROFINET CBA / remote connection / with cyclic transmission |
Refresh time / of the remote interconnections / with PROFINET CBA / with cyclical transfer |
8 ms |
Number of remote connections to input variables / with PROFINET CBA / with cyclical transfer / maximum |
200 |
Number of remote connections to output variables / with PROFINET CBA / with cyclical transfer / maximum |
200 |
Amount of data |
|
● as user data for remote interconnections with input variables / with PROFINET CBA / with cyclical transfer / maximum |
2000 byte |
● as user data for remote interconnections with output variables / with PROFINET CBA / with cyclical transfer / maximum |
2000 byte |
Performance data / PROFINET CBA / HMI variables via PROFINET / acyclic |
Number of connectable HMI stations / for HMI variables / in the case of acyclic transmission / with PROFINET CBA |
3 |
Refresh time / of the HMI variables / in the case of acyclic transmission / with PROFINET CBA |
500 ms |
Number of HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum |
200 |
Amount of data / as user data for HMI variables / in the case of acyclic transmission / with PROFINET CBA / maximum |
8 Kibyte |
Performance data / PROFINET CBA / device-internal connections |
Number of internal connections / with PROFINET CBA / maximum |
256 |
Amount of data / of the internal connections / with PROFINET CBA / maximum |
2400 byte |
Performance data / PROFINET CBA / connections to constants |
Number of connections with constants / with PROFINET CBA / maximum |
200 |
Amount of data / as user data for interconnections with constants / with PROFINET CBA / maximum |
4096 byte |
Performance data / PROFINET CBA / PROFIBUS proxy functionality |
Product function / with PROFINET CBA / PROFIBUS proxy functionality |
No |
Performance data / telecontrol |
Protocol / is supported |
|
● TCP/IP |
Yes |
Product functions / management, configuration |
Product function / MIB support |
Yes |
Protocol / is supported |
|
● SNMP v1 |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
Configuration software |
|
● required |
STEP 7 V5.3 SP2 or higher |
● for PROFINET CBA / required |
SIMATIC iMap V2.0 SP1 and higher |
Identification & maintenance function |
|
● I&M0 - device-specific information |
Yes |
● I&M1 – higher-level designation/location designation |
Yes |
Product functions / Diagnosis |
Product function / Web-based diagnostics |
Yes |
Product functions / switch |
Product feature / Switch |
No |
Product functions / Redundancy |
Product function |
|
● Ring redundancy |
No |
Product functions / Security |
Product function |
|
● ACL - IP-based |
Yes |
● ACL - IP-based for PLC/routing |
No |
● switch-off of non-required services |
No |
● Blocking of communication via physical ports |
No |
● log file for unauthorized access |
No |
Product functions / Time |
Product function / SICLOCK support |
Yes |
Product function / pass on time synchronization |
Yes |
Protocol / is supported / NTP |
Yes |
Further Information / Internet Links |
Internet-Link |
|
● to website: Selector SIMATIC NET SELECTION TOOL |
http://www.siemens.com/snst |
● to website: Industrial communication |
http://www.siemens.com/simatic-net |
● to website: Information and Download Center |
http://www.siemens.com/automation/net/catalog |
● to website: Image database |
http://automation.siemens.com/bilddb |
● to website: CAx Download Manager |
http://www.siemens.com/cax |
● to website: Industry Online Support |
http://support.automation.siemens.com |
last modified: |
03.11.2014 |
Date 04.11.2014 |