6ES7675-3AG30-0QA0 SIMATIC MICROBOX 420-T

Product Code: 6ES7675-3AG30-0QA0

Availability: In Stock

Price: $2,856.45
Artikelnummer 6ES7675-3AG30-0QA0
SIMATIC MICROBOX 420-T, WITH SIMATIC WINAC RTX 2005, TECHNOLOGY/MOTION CONTROL-FUNC. AND SIMATIC SOFTNET PG, INSTALLED READY TO RUN ON MICROBOX PC420 WITH PIII 933 MHZ, PROFIBUS DP, 512 MB RAM, 2 GB CF-CARD WINDOWS XP EMBEDDED, LANGUAGE ENGLISCH
General information
Hardware product version V1
Firmware version V1.0 + SP1
PC configuration
Computer platform Microbox PC 420
Processor selection P III 933 MHz
Main memory 512 Mbyte RAM
Compact Flash 2 Gbyte
Operating systems Windows XP embedded SP2
Installed software
● Control WinAC T V1.0 SP1
● Communication SOFTNET LEAN for IE/SIMATIC NET 2005 V3.0.1
Supply voltage
Rated value, 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Rated value at 24 V DC 2 500 mA
Power
Power consumption, max. 61 W
Battery
Backup battery
● Backup time, max. 5 y
CPU processing times
for bit operations, typ. 0.004 µs
for fixed point arithmetic, typ. 0.003 µs
for floating point arithmetic, typ. 0.004 µs
CPU-blocks
DB
● Number, max. 65 535
● Size, max. 64 kbyte
FB
● Number, max. 65 536
● Size, max. 64 kbyte
FC
● Number, max. 65 536
OB
● Number, max. 30
● Size, max. 64 kbyte
● Number of free cycle OBs 1
● Number of time alarm OBs 1
● Number of delay alarm OBs 1
● Number of time interrupt OBs 9
● Number of process alarm OBs 1
● Number of startup OBs 1
● Number of asynchronous error OBs 7
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
● additional within an error OB 2
Counters, timers and their retentivity
S7 counter
● Number 512
Retentivity
— can be set Yes
— lower limit 0
— upper limit 512
— preset 8
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number 3
S7 times
● Number 512
Retentivity
— can be set Yes
— lower limit 0
— upper limit 512
— preset 0
Time range
— lower limit 10 ms
— upper limit 6 390 s
IEC timer
● present Yes
● Type SFB
● Number 3
Data areas and their retentivity
retentive data area, total 30 KB
retentive data area in total (incl. times, counters, flags), max. 30 kbyte
Flag
● Number, max. 16 384 byte
● Number of clock memories 8
Data blocks
● Number, max. 65 535
● Size, max. 64 kbyte
● Retentivity adjustable Yes
● Retentivity preset Yes
Local data
● adjustable, max. 16 kbyte
● preset 256 byte
● per priority class, max. 20 byte
Address area
I/O address area
● Inputs 2 000 byte
● Outputs 2 048 byte
Process image
● Inputs 2 048 byte
● Outputs 2 048 byte
● Inputs, adjustable 2 048 kbyte
● Outputs, adjustable 2 048 kbyte
● Inputs, default 512 byte
● Outputs, default 512 byte
Subprocess images
● Number of subprocess images, max. 15
Digital channels
● Inputs 16 000
● Outputs 16 376
● Inputs, of which central 0
● Outputs, of which central 0
Analog channels
● Inputs 1 000
● Outputs 1 023
● Inputs, of which central 0
● Outputs, of which central 0
Addressing volume
● Inputs 2 048 byte
● Outputs 2 048 byte
Address space per module
● Address space per module, max. 244 byte
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable No
● Deviation per day, max. 5 s
● Backup time 5 y
Operating hours counter
● Number 8
● Number/Number range 0 to 7
● Range of values 32767
● Granularity 1 hour
● retentive Yes
Clock synchronization
● supported No
● to PC-CP, slave No
● to MPI, master No
● to MPI, slave No
● in AS, master No
● in AS, slave No
● on Ethernet via NTP No
Digital inputs
integrated channels (DI) 0
Digital outputs
Number of digital outputs 8
● of which high-speed outputs 8
integrated channels (DO) 8
Functions For technology functions, e.g. high-speed cam switch signals
short-circuit protection Yes
Switching capacity of the outputs
● Lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 Ω
Output voltage
● for signal "0", max. 3 V
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, min. 5 mA
● for signal "1" permissible range, max. 0.6 A
Parallel switching of 2 outputs
● for increased power No
● for redundant control of a load No
Switching frequency
● with resistive load, max. 1 000 Hz
● with inductive load, max. 0.2 Hz
● on lamp load, max. 10 Hz
Cable length
● Cable length, shielded, max. 25 m
● Cable length unshielded, max. 25 m
Analog inputs
Integrated channels (AI) 0
Analog outputs
Integrated channels (AO) 0
Interfaces
USB port 2xUSB 2.0 high curr./2xUSB 2.0 low curr.
serial interface COM1 (RS232)
Video interfaces
● Graphics interface DVI VGA / DVI integrated
Industrial Ethernet
● Industrial Ethernet interface 2x VUA VT6105L OM/VT6106S, 10/100 Mbit/s with RJ45
1st interface
Physics RS 485
Isolated Yes
Functionality
● MPI No
● DP master Yes
● DP slave No
● Point-to-point connection No
DP master
● Number of connections, max. 14
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— S7 communication, as client Yes
— S7 communication, as server Yes
— Equidistance mode support No
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 Yes
User data per DP slave
— User data per DP slave, max. 244 byte
— Inputs, max. 244 byte
— Outputs, max. 244 byte
2nd interface
Physics RS 485
Isolated Yes
Automatic detection of transmission speed Yes
Functionality
● MPI No
● DP master Yes
● DP slave No
● PROFINET IO Controller No
● PROFINET CBA No
● Point-to-point connection No
DP master
● Number of connections, max. 0
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication No
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication No
— S7 communication, as client No
— S7 communication, as server No
— Equidistance mode support Yes
— SYNC/FREEZE No
— Activation/deactivation of DP slaves No
— Direct data exchange (slave-to-slave communication) No
— DPV1 Yes
User data per DP slave
— User data per DP slave, max. 244 byte
— Inputs, max. 244 byte
— Outputs, max. 244 byte
Communication functions
PG/OP communication Yes
Global data communication
● supported No
S7 basic communication
● supported No
S7 communication
● supported Yes
● as server Yes
● As client Yes
● User data per job, max. 64 kbyte
● User data per job (of which consistent), max. 64 kbyte
S5-compatible communication
● supported No
Standard communication (FMS)
● supported No
Open IE communication
● TCP/IP No
● ISO-on-TCP (RFC1006) No
● UDP No
Number of connections
● overall 64
● usable for PG communication 63
— reserved for PG communication 1
● usable for OP communication 63
— reserved for OP communication 1
● usable for S7 basic communication 0
● usable for S7 communication 62
● usable for routing 62
S7 message functions
Number of login stations for message functions, max. 32
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 200
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 20
Status/control
● Status/control variable Yes
● Variables I/O/F/DB/C/
Forcing
● Forcing No
Diagnostic buffer
● present Yes
● Number of entries, max. 120
— can be set Yes
— preset 120
Interrupts/diagnostics/status information
Alarms
● Alarms No
Diagnostic messages
● Diagnostic functions No
Diagnostics indication LED
● Status indicator digital output (green) No
● Status indicator digital input (green) No
Degree and class of protection
Degree of protection to EN 60529
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
cULus Yes
RCM (formerly C-TICK) Yes
FM approval No
Ambient conditions
Operating temperature
● Min. 0 °C
● max. 50 °C
Storage/transport temperature
● Min. -20 °C
● max. 60 °C
Vibrations
● Operation, checked according to IEC 60068-2-6 Yes
● Transport tested checked to IEC 60068-2-6 Yes
Shock test
● checked according to IEC 60068-2-27 Yes
● checked according to IEC 60068-2-29 Yes
Shock testing
● checked according to IEC 60068-2-29 Yes
● Operation, checked according to IEC 60068-2-29 Yes
Configuration
Configuration software
● STEP 7 Yes
programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) See manual
● System function blocks (SFB) See manual
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Software libraries
— Process diagnostics Yes
— Software controller Yes
Know-how protection
● User program protection/password protection Yes
Cycle time monitoring
● lower limit 1 ms
● upper limit 6 000 ms
● can be set Yes
● preset 6 000 ms
Technology objects
● Number of technology objects, total 64
— of which axes 32
— of which output cams 32
— of which cam disks 32
● Number of probes 16
● Number of external encoders 16
Dimensions
Width 262 mm
Height 133 mm
Depth 65 mm
last modified: 13.10.2014