6ES7671-0RC05-0YA0 SIMATIC WINAC RTX 2005,

Product Code: 6ES7671-0RC05-0YA0

Availability: In Stock

Price: $842.55
Artikelnummer 6ES7671-0RC05-0YA0
SIMATIC WINAC RTX 2005, SINGLE LICENSE F. 1 INSTALL., R-SW, SW AND DOCU. ON CD, LICENSE KEY ON FD, CLASS A, 3 LANGUAGES (D,E,F), EXECUTABLE UNDER WIN 2000/XP AND ARDENCE RTX, REFERENCE-HW: SIMATIC PC
General information
Firmware version 4,3
Memory
Work memory
● Integrated PC RAM can be used (non-paged memory)
Load memory
● integrated RAM, max. PC RAM can be used (non-paged memory)
CPU processing times
for bit operations, typ. 0.004 µs; Typical
for fixed point arithmetic, typ. 0.003 µs; Typical
for floating point arithmetic, typ. 0.004 µs; Typical
Reference platform Pentium 4, 2.4 GHz
CPU-blocks
DB
● Number, max. Limited only by available PC work memory
● Size, max. 64 kbyte
FB
● Number, max. Limited only by available PC work memory
● Size, max. 64 kbyte
FC
● Number, max. Limited only by available PC work memory
● Size, max. 64 kbyte
OB
● Size, max. 64 kbyte
● Number of time alarm OBs 1
● Number of delay alarm OBs 1
● Number of time interrupt OBs 9
● Number of process alarm OBs 1
Nesting depth
● per priority class 24
● additional within an error OB 24
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— can be set Yes
— lower limit 0
— upper limit 2 047
— preset 8
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
S7 times
● Number 2 048
Retentivity
— lower limit 0
— upper limit 2 047
— preset 0
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
Data areas and their retentivity
Retentivity without UPS and PS Extension Board 128 KB with SIMATIC Microbox PC 427B and Panel PC 477B; other SIMATIC PCs on request
Retentivity with UPS all data
Flag
● Number, max. 16 kbyte
● of which retentive MB 0 to MB 16383
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8
Address area
I/O address area
● Inputs 16 kbyte
● Outputs 16 kbyte
of which, distributed
— DP interface, inputs 16 kbyte
— DP interface, outputs 16 kbyte
Process image
● Inputs, adjustable 8 kbyte
● Outputs, adjustable 8 kbyte
● Inputs, default 512 byte
● Outputs, default 512 byte
Subprocess images
● Number of subprocess images, max. 15
Digital channels
● Inputs 128 000
● Outputs 128 000
Analog channels
● Inputs 8 000
● Outputs 8 000
Hardware configuration
Submodules
● Number of submodules, max 4
● of which PROFIBUS, max. 4; CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC, CP 5613 CP, 5613-A2
Number of operable FMs and CPs (recommended)
● FM FM distributed: FM 350-1 / 350-2, FM 351, FM 352, FM 353, FM 355 / 355-2
● CP, point-to-point CP 340, CP 341 distributed
● CP, LAN Over PC CP
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
Clock synchronization
● supported Yes
● to PC-CP, slave Yes
Interfaces
1st interface
Interface type CP 5611, CP 5611-A2, integrated PROFIBUS interface of the SIMATIC PC
Max. no. of simultaneously operable CPs 1
Physics RS 485 / PROFIBUS
Isolated Yes
Functionality
● MPI No
● DP master Yes
● DP slave No
DP master
● Number of connections, max. 8
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 64
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— Equidistance mode support Yes; Only in conjunction with isochronous mode
— Isochronous mode Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV0 Yes
— DPV1 Yes
Address area
— Inputs, max. 16 kbyte
— Outputs, max. 16 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
2nd interface
Interface type CP 5613, CP 5613-A2
Max. no. of simultaneously operable CPs 4
Physics RS 485 / PROFIBUS
Isolated Yes
Functionality
● MPI No
● DP master Yes
● DP slave No
DP master
● Number of connections, max. 50
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 125
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— Equidistance mode support Yes; Only in conjunction with isochronous mode
— Isochronous mode Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV0 Yes
— DPV1 Yes
Address area
— Inputs, max. 16 kbyte
— Outputs, max. 16 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Number of DP masters with isochronous mode 2
User data per isochronous slave, max. 128 byte
equidistance Yes
shortest clock pulse 2.2 ms; 2.2 ms without partial process image; 2.2 ms with partial process image
Communication functions
PG/OP communication Yes
Global data communication
● supported No
S7 basic communication
● supported No
S7 communication
● as server Yes
● As client Yes
Number of connections
● overall 64
● usable for PG communication
— reserved for PG communication 1
● usable for OP communication
— reserved for OP communication 1
S7 message functions
Number of login stations for message functions, max. 62
SCAN procedure No
Process diagnostic messages Yes; Alarm_S
Alarm 8-blocks Yes
Process control messages No
Test commissioning functions
Status block Yes
Single step Yes
Status/control
● Status/control variable Yes
Forcing
● Forcing No
Diagnostic buffer
● present Yes
● Number of entries, max.
— preset 120
Hardware requirements
Hardware required PC with color monitor, keyboard, mouse or pointing device for Windows
Main memory, min. 256 Mbyte
Required memory on hard disk, min. 100 Mbyte
Processor Intel Pentium 400 MHz
● Multi-processor system Yes; Dual Pentium, CoreDuo, Core2Duo
● Hyper-threading Yes
Operating systems
Configuration
Configuration software
● STEP 7 Yes; V5.3 SP3 or higher, Engineering Tools (optional)
programming
● Nesting levels 8
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Software libraries
— Easy Motion Control Yes
Know-how protection
● User program protection/password protection Yes
Open Development interfaces
● CCX (Custom Code Extension) Yes; With WinAC ODK V4.1
● CMI (Controller Management Interface) Yes; With WinAC ODK V4.1
● SMX (Shared Memory Extension) Yes; With WinAC ODK V4.1
— Inputs 4 kbyte
— Outputs 4 kbyte
last modified: 14.10.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: