6ES7626-1DG04-0AE3 SIMATIC C7-626/P, COMPACT UNIT

Product Code: 6ES7626-1DG04-0AE3

Availability: In Stock

Price: $2,692.05
  
 

SIMATIC C7-626/P, COMPACT UNIT WITH INTEGRATED COMPONENTS: S7-300 CPU 315 (96KB MEMORY), SIMATIC OP25 AND IM 360, 16 DI, 16 DO, 4 AI, 4AO, 4UI
Operator control and monitoring
Password protection Yes
Password levels 9
Graphics object
Character graphics Yes
Full graphics Yes; Access to external editors
Process images
Number of process images depending on user memory
Number of variables in message text, max. 8
Operating/fault messages
Number of entries in operational log, max. 512; Entries in ring buffer
Operating messages, max. 2000; depending on user memory
Scroll operating messages, max. 512
Alarm messages Yes
Number of fault message, max. 2000; depending on user memory
Number of entries in fault message buffer, max. 512; Entries in ring buffer
Number of symbol/character sets 4
Recipes
Number of recipes, max. 255
Data records per recipe, max. 500
Entries per data record, max. 500
Recipe data memory, max. 64 kbyte
Display
Design of display LC-Display, CCFL-backlit, passive mono; active display area 105 x 79 mm
dynamic objects Input, output, input/output fields, date/time fields, symbolic input/output fields, bar graphs, characteristics, pictorial presentation etc.
Resolution (pixels)
horizontal image resolution 320
vertical image resolution 240
Backlighting
MTBF backlighting (at 20 °C) 20000 h; about 2.2 years
Control elements
Keyboard fonts
Number of function keys 10
Number of softkeys 14
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 30.2 V
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
Current consumption, typ. 700 mA
Current consumption, max. 2 A
Power loss
Power loss, typ. 17 W
Memory
Work memory
integrated 96 kbyte; RAM 96 KB/32 K instructions (integrated); 2 MB dyn. RAM
Load memory
integrated FEPROM, max. 512 kbyte
integrated RAM, max. 180 kbyte
Backup
present Yes
with battery Yes; all data
without battery Yes; 4736 Byte: parameterizable for memory bits, times, counters, data
CPU processing times
for bit operations, typ. 0.3 µs
for bit operations, max. 0.6 µs
for word operations, typ. 1 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 50 µs
for timer/counter operations, typ. 12 µs
CPU-blocks
DB
Number, max. 255; DB 0 reserved
FB
Number, max. 192; see instruction list
FC
Number, max. 192; see instruction list
OB
Number, max. see instruction list
Number of free cycle OBs 1; OB 1
Number of time alarm OBs 1; OB 10
Number of time interrupt OBs 1; OB 35
Number of process alarm OBs 1; OB 40
Number of startup OBs 1; OB 100
Number of asynchronous error OBs 8; OB 80, 81, 82, 85, 86, 87, 121, 122
Nesting depth
per priority class 8
Counters, timers and their retentivity
S7 counter
Number 64
of which retentive with battery
adjustable Yes
lower limit 0
upper limit 63
of which retentive without battery
adjustable Yes
lower limit 0
upper limit 63
Counting range
lower limit 0
upper limit 999
S7 times
Number 128
of which retentive with battery
adjustable Yes
lower limit 0
upper limit 127
of which retentive without battery
adjustable Yes
lower limit 0
upper limit 127
Time range
lower limit 10 ms
upper limit 9990 s
Data areas and their retentivity
Flag
Number, max. 256 byte
Retentivity available Yes
of which retentive with battery 0 to 2047
of which retentive without battery 0 to 2047
Address area
I/O address area
Inputs 1 kbyte
Outputs 1 kbyte
Process image
Inputs 128 byte
Outputs 128 byte
Hardware configuration
Number of modules per system, max. 8
Number of modules per DP slave interface, max. 32; 122 byte address space per DP station
connectable programming devices/PCs SIMATIC PG/PC, standard PC
Interface modules
Interface module IM 360 integrated Yes
Number of DP masters
integrated 0
via CP 1; CP 342-5
Number of operable FMs and CPs (recommended)
FM 8
CP, point-to-point 4
CP, LAN 2
Expansion modules
Number of expansion modules, max. 24
Analog inputs/outputs, max. 192
Digital inputs/outputs, max. 768
Rack
Modules per rack, max. 8
Rack, number of rows, max. 3
Time of day
Clock
Hardware clock (real-time clock) Yes
Digital inputs
Number of digital inputs 16
Input voltage
Rated value, DC 1 V
for signal "1" 15 to 30 V
Input current
for signal "1", typ. 11.5 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max. 4.8 ms; typically 3 ms
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Digital outputs
Number of digital outputs 16
Short-circuit protection Yes; Clocked electronically
Limitation of inductive shutdown voltage to 48 V
Switching capacity of the outputs
Lamp load, max. 5 W
Output voltage
for signal "1", min. L+ (-0.8 V)
Output current
for signal "1" rated value 0.5 A
for signal "1" minimum load current 5 mA
for signal "0" residual current, max. 0.5 mA
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
Total current of the outputs (per group)
all mounting positions
up to 20 °C, max. 4 A
up to 40 °C, max. 2 A
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Universal inputs
Number of universal inputs 4
usable as UI1, UI2: Digital/alarm input 24 V DC or up/down counter; UI3: Digital/alarm input 24 V DC or up/down counter or frequency/period duration counter; UI4: Digital/alarm input 24 V DC
Counter frequency, max. 10 kHz
Input voltage
Rated value (DC) 24 V
Input current
for signal "1" typ. 11.5 mA
Cable length
Cable length, shielded, max. 1000 m
Analog inputs
Number of analog inputs 4
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 30 mA
Cycle time (all channels), typ. 2 ms
Input ranges
Voltage Yes
Current Yes
Input ranges (rated values), voltages
-10 V to +10 V Yes
Input resistance (-10 V to +10 V) 50 kΩ
Input ranges (rated values), currents
-20 to +20 mA Yes
Input resistance (-20 to +20 mA) 105.5 Ω
4 to 20 mA Yes
Input resistance (4 to 20 mA) 105.5 Ω
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 16 V; +/-
Cycle time (all channels) max. 4 ms; typ. 2 ms
Output ranges, voltage
-10 to +10 V Yes
Output ranges, current
-20 to +20 mA Yes
4 to 20 mA Yes
Load impedance (in rated range of output)
with voltage outputs, min. 2 kΩ
with voltage outputs, capacitive load, max. 1 µF
with current outputs, max. 0.5 kΩ
with current outputs, inductive load, max. 1 mH
Cable length
Cable length, shielded, max. 200 m
Analog value generation
Integration and conversion time/resolution per channel
Resolution with overrange (bit including sign), max. 12 bit
Conversion time (per channel) 0.5 ms
Settling time
for resistive load 0.1 ms
for capacitive load 3.3 ms
for inductive load 0.5 ms
Encoder
Connectable encoders
2-wire sensor Yes
permissible quiescent current (2-wire sensor), max. 2 mA
Errors/accuracies
Operational error limit in overall temperature range
Voltage, relative to input area, (+/-) 0.8 %
Current, relative to input area, (+/-) 0.8 %
Voltage, relative to output area, (+/-) 0.8 %
Current, relative to output area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
Voltage, relative to input area, (+/-) 0.6 %
Current, relative to input area, (+/-) 0.6 %
Voltage, relative to output area, (+/-) 0.5 %
Current, relative to output area, (+/-) 0.6 %
Interfaces
Number of printer interfaces 1; RS 232
MPI
Cable length, max. 9100 m; without repeaters 50 m; with 2 repeaters: 1100 m; with 10 repeaters in series: 9100 m; via fiber optic cable: 23.8 km (with star hubs or OLMs)
1. Interface
Functionality
MPI Yes
DP master No
DP slave No
MPI
Number of nodes, max. 32; PG/PC, OP, C7, S7-300/400, M7
Transmission rate, max. 187.5 kbit/s
Communication functions
PG/OP communication Yes
Global data communication
supported Yes
S7 basic communication
supported Yes
S7 communication
S7 extended communication Yes; Server
S5 compatible communication
supported Yes
Standard communication (FMS)
supported Yes; occupies 2 nodes per device (1 x CPU, 1 x OP)
Number of connections
overall
of which dynamic 8
of which static 4
Interrupts/diagnostics/status information
Substitute values connectable Yes; Parameterizable
Alarms
Alarm cycle Yes; Parameterizable
Diagnostic alarm Yes; parameterizable for parameter errors, measuring range exceeded, wire break detection at 4 to 20 mA via software
Diagnostic messages
Diagnostic functions Yes
Counter
Number of counter inputs 3; UE1, UE2, UE3
Principle Counting of edges
Counting range, description UI1, UI2: up: 0 to 65535, down: 65535 to 0; UI3: up: 0 to 16777215, down: 16777215 to 0
Counting alarm backward counter on reaching "0"
Counting alarm forward counter on reaching limit value
Enable In the program
Limit value (setpoint) default one counter per value
Frequency counter
Number of frequency counters 1; UI3
Principle Counting of pulses within a time period
Gate width, adjustable Yes
Gate width 0.1 / 1 / 10 s
Counting range 0 to 16777215
Cycle duration counter
Number 1; UI3
Cycle duration, max. 8.38 s; or 0.12 Hz
Principle Counting of fixed time units between two positive edges
Gate width 0.1 / 1 / 10 s (adjustable)
Counting range, lower limit 0
Counting range, upper limit 16777214
Galvanic isolation
Galvanic isolation digital inputs
Galvanic isolation digital inputs Yes
between the channels, in groups of 16
Galvanic isolation digital outputs
Galvanic isolation digital outputs Yes; Optocoupler
between the channels, in groups of 8
Galvanic isolation analog inputs
Galvanic isolation analog inputs Yes; shared with AO
Galvanic isolation analog outputs
Galvanic isolation analog outputs Yes; shared with AI
Galvanic isolation channels
Galvanic isolation universal inputs No
Isolation
Isolation tested with 500 V DC
EMC
Emission of radio interference acc. to EN 55 022
Interference emission acc. to EN 55022, class A Yes; Noise emission: Class A / EN 55022; conducted interference: IEC 1000-4-4, IEC 1000-4-5; noise immunity: IEC 1000-4-2, IEC 1000-4-3, IEC 1000-4-4, IEC 1000-4-6, EN 50140
Degree and class of protection
IP20 Yes; Housing
IP65 Yes; Front
Standards, approvals, certificates
DIN/ISO 9001 Yes; Certification of production and development
CSA approval Yes; C22.2 Number 142
UL approval Yes; UL 508
FM approval Yes; FM-Standards No. 3611, 3600, 3810 Class I, Division 2, Group A, B, C, D
developed in accordance with IEC 61131 Yes; EN 61131-2 (IEC 1131-2)
Ambient conditions
Operating temperature
45 degree installation, min. 0 °C
45 degree installation, max. 30 °C
horizontal installation, min. 0 °C
horizontal installation, max. 45 °C; possible with forced ventilation
vertical installation, min. 0 °C
vertical installation, max. 45 °C
Air pressure
permissible range, min. 795 hPa
permissible range, max. 1080 hPa
Relative humidity
Operation, min. 5 %
Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
Operation, tested according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 58 Hz; (constant amplitude 0.075 mm); 58 to 500 Hz; (constant acceleration 9.8 m/s2)
Shock test
tested according to IEC 60068-2-29 Yes; IEC 68, Part 2-29 half-sine: 100 m/s2 (10 g), 16 ms, 100 shocks
Configuration
Configuration software
STEP 7 Yes
STEP 7 Mini Yes
ProTool Yes
ProTool/Pro Yes
Programming
Command set see instruction list
Nesting levels 8
Program organization Linear, structured
System functions (SFC) see instruction list
Programming language
LAD Yes
FBD Yes
STL Yes
SCL Yes
CFC Yes
GRAPH Yes
HiGraph® Yes
Software libraries
Process diagnostics Yes; S7-CPU and C7-OP
Software controller Yes; 16 circles
Know-how protection
User program protection/password protection Yes
Cycle time monitoring
lower limit 1 ms
upper limit 6000 ms
adjustable Yes
preset 150 ms
Languages
Online languages
Number of online/runtime languages 3
Dimensions
Width 240 mm
Height 168 mm
Depth 69 mm
Mounting cutout/device depth (W x H x D)
Mounting cutout, width 231 mm
Mounting cutout, height 159 mm
Weights