SIMATIC S7-400, SM 431 ANALOG INPUT MODULE OPTIC. ISOLATED, 16 AI, 16 BIT RESOLUTION, U/I/RESIST./ THERMOEL./PT100,ALARM,DIAGNOST. |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V; Only required for supplying 2-wire transmitters |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
400 mA |
from backplane bus 5 V DC, max. |
700 mA |
Power losses |
Power loss, typ. |
4.5 W |
Hardware configuration |
Slots |
● Required slots |
1 |
Analog inputs |
Number of analog inputs |
16 |
Number of analog inputs for voltage/current measurement |
16 |
Number of analog inputs for resistance measurement |
8 |
permissible input voltage for voltage input (destruction limit), max. |
18 V; 18 V continuous, 75 V for 1 ms (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
Yes |
● Resistance thermometer |
Yes |
● Resistance |
Yes |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
1 MΩ |
● -1 V to +1 V |
Yes |
● Input resistance (-1 V to +1 V) |
1 MΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
1 MΩ |
● -2.5 V to +2.5 V |
Yes |
● Input resistance (-2.5 V to +2.5 V) |
1 MΩ |
● -25 mV to +25 mV |
Yes |
● Input resistance (-25 mV to +25 mV) |
1 MΩ |
● -250 mV to +250 mV |
Yes |
● Input resistance (-250 mV to +250 mV) |
1 MΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
1 MΩ |
● -50 mV to +50 mV |
Yes |
● Input resistance (-50 mV to +50 mV) |
1 MΩ |
● -500 mV to +500 mV |
Yes |
● Input resistance (-500 mV to +500 mV) |
1 MΩ |
● -80 mV to +80 mV |
Yes |
● Input resistance (-80 mV to +80 mV) |
1 MΩ |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
50 Ω |
● -10 to +10 mA |
Yes |
● Input resistance (-10 to +10 mA) |
50 Ω |
● -20 to +20 mA |
Yes |
● Input resistance (-20 to +20 mA) |
50 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
50 Ω |
● -5 to +5 mA |
Yes |
● Input resistance (-5 to +5 mA) |
50 Ω |
Input ranges (rated values), thermoelements |
● Type B |
Yes |
● Type E |
Yes |
● Type J |
Yes |
● Type K |
Yes |
● Type L |
Yes |
● Type N |
Yes |
● Type R |
Yes |
● Type S |
Yes |
● Type T |
Yes |
● Type U |
Yes |
Input ranges (rated values), resistance thermometer |
● Ni 100 |
Yes |
● Input resistance (Ni 100) |
1 MΩ |
● Ni 1000 |
Yes |
● Input resistance (Ni 1000) |
1 MΩ |
● Pt 100 |
Yes |
● Input resistance (Pt 100) |
1 MΩ |
● Pt 1000 |
Yes |
● Input resistance (Pt 1000) |
1 MΩ |
● Pt 200 |
Yes |
● Input resistance (Pt 200) |
1 MΩ |
● Pt 500 |
Yes |
● Input resistance (Pt 500) |
1 MΩ |
Input ranges (rated values), resistors |
● 0 to 150 ohms |
Yes |
● Input resistance (0 to 150 ohms) |
1 MΩ |
● 0 to 300 ohms |
Yes |
● Input resistance (0 to 300 ohms) |
1 MΩ |
● 0 to 48 ohms |
Yes |
● Input resistance (0 to 48 ohms) |
1 MΩ |
● 0 to 600 ohms |
Yes |
● Input resistance (0 to 600 ohms) |
1 MΩ |
● 0 to 6000 ohms |
Yes; Usable up to 5000 Ohm |
● Input resistance (0 to 6000 ohms) |
1 MΩ |
Thermocouple (TC) |
Temperature compensation |
— external temperature compensation with compensations socket |
Yes |
— external temperature compensation with Pt100 |
Yes |
— dynamic reference temperature value |
Yes |
Characteristic linearization |
● Parameterizable |
Yes |
— for thermocouples |
Type B, E, J, K, L, N, R, S, T, U |
— for resistance thermometer |
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni1000 |
Cable length |
● Cable length, shielded, max. |
200 m; 50 m with thermocouples and input ranges <= 80 mV |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; 16 / 16 / 16 |
● Integration time, parameterizable |
Yes |
● Basic conversion time, ms |
6 / 20,1 / 23,5 ms |
● Integration time, ms |
2,5 / 16,7 / 20 ms |
● Basic conversion time, including integration time, ms |
|
— additional conversion time for wire break monitoring |
4.3 / 4.3 / 4.3 ms |
— additional conversion time for resistance measurement |
12 / 40,2 / 47 ms |
— additional conversion time for wire break monitoring and resistance measurement |
5,5 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
● for resistance measurement with two-wire connection |
Yes; Line resistances are also measured |
● for resistance measurement with three-wire connection |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.3 %; +/-0.3% at +/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/- 10 V; +/-0.31% at +/-80 mV; +/-0.32% at +/-50 mV; +/-0.35% at +/-25 mV; |
● Current, relative to input area, (+/-) |
0.3 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA |
● Resistance, relative to input area, (+/-) |
0.3 %; +/-0.3% at 0 to 48 Ohm (4-conductor measurement), 0 to 150 Ohm (4-conductor measurement), 0 to 300 Ohm (4-conductor measurement), 0 to 600 Ohm (4-conductor measurement), 0 to 5000 Ohm (4-conductor measurement, in range of 6000 Ohm); +/-0.4% at 0 to 300 Ohm (3-conductor measurement), 0 to 600 Ohm (3-conductor measurement), 0 to 5000 Ohm (3-conductor measurement, in range of 6000 Ohm); |
● Resistance thermometer, relative to input area, (+/-) |
0.4 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.15 %; +/-0.15% at +/-250 mV, +/-500 mV, +/-1 V, +/-2.5 V, +/-5 V, 1 to 5 V, +/-10 V; +/-0.17% at +/-80 mV; +/-0.19% at +/-50 mV; +/-0.23% at +/-25 mV; |
● Current, relative to input area, (+/-) |
0.15 %; at 0 to 20 mA, +/-5 mA, +/-10 mA, +/- 20 mA, 4 to 20 mA |
● Resistance, relative to input area, (+/-) |
0.15 %; +/-0.15% at 0 to 48 ohms (4-conductor measurement), 0 to 150 ohms (4-conductor measurement), 0 to 300 ohms (4-conductor measurement), 0 to 5000 ohms (4-conductor measurement, in range of 6000 ohms); +/-0.3% at 0 to 300 ohms (3-conductor measurement), 0 to 600 ohms (3-conductor measurement), 0 to 5000 ohms (3-conductor measurement, in range of 6000 ohms) |
● Resistance thermometer, relative to input area, (+/-) |
0.3 % |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable |
● Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostics |
Yes; Parameterizable |
Galvanic isolation |
Galvanic isolation analog inputs |
● Galvanic isolation analog inputs |
Yes; internal/external |
● between the channels |
No |
Permissible potential difference |
between the inputs (UCM) |
120 V AC |
Isolation |
Isolation checked with |
2120 V DC between bus and L+/M; 2120 V DC between bus and analog part; 500 V DC between bus and local ground; 707 V DC between analog part and L+/M; 2120 V DC between analog part and local ground; 2120 V DC between L+/M and local ground |
Dimensions |
Width |
25 mm |
Height |
290 mm |
Depth |
210 mm |
Weights |
Weight, approx. |
500 g |
last modified: |