Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
from load voltage L+ (without load), max. |
270 mA |
from backplane bus 5 V DC, max. |
75 mA |
Power losses |
Power loss, typ. |
5.5 W |
Power loss, max. |
6.9 W |
Digital inputs |
Number of digital inputs |
8 |
Input characteristic curve in accordance with IEC 61131, type 2 |
Yes |
Input voltage |
● Rated value, DC |
24 V |
Input current |
● for signal "1", typ. |
7 mA |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
8 |
short-circuit protection |
Yes |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Load resistance range |
● lower limit |
240 Ω |
● upper limit |
4 kΩ |
Output current |
● for signal "1" rated value |
0.1 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
5 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
150 mA |
● for signal "0" residual current, max. |
0.5 mA |
Parallel switching of 2 outputs |
● for logic links |
Yes |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
100 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
400 mA |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Analog inputs |
Number of analog inputs |
4 |
permissible input voltage for voltage input (destruction limit), max. |
20 V |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
Yes |
● Resistance thermometer |
Yes |
Input ranges (rated values), voltages |
● 0 to +10 V |
Yes |
● Input resistance (0 to 10 V) |
100 kΩ |
● -1.75 to +11.75 V |
Yes |
● Input resistance (-1.75 to +11.75 V) |
100 kΩ |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
50 Ω |
● 0 to 23.5 mA |
Yes |
● Input resistance (0 to 23.5 mA) |
50 Ω |
● -3.5 to +23.5 mA |
Yes |
● Input resistance (-3.5 to +23.5 mA) |
50 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
50 Ω |
Input ranges (rated values), thermoelements |
● Type B |
Yes |
● Input resistance (Type B) |
10 MΩ |
● Type E |
Yes |
● Input resistance (Type E) |
10 MΩ |
● Type J |
Yes |
● Input resistance (type J) |
10 MΩ |
● Type K |
Yes |
● Input resistance (Type K) |
10 MΩ |
● Type R |
Yes |
● Input resistance (Type R) |
10 MΩ |
● Type S |
Yes |
● Input resistance (Type S) |
10 MΩ |
Input ranges (rated values), resistance thermometer |
● Pt 100 |
Yes |
● Input resistance (Pt 100) |
10 MΩ |
Thermocouple (TC) |
Temperature compensation |
— internal temperature compensation |
Yes |
— external temperature compensation with Pt100 |
Yes |
Characteristic linearization |
● Parameterizable |
Yes |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
14 bit |
● Conversion time (per channel) |
100 ms |
Settling time |
● for resistive load |
0.1 ms |
● for capacitive load |
3.3 ms |
● for inductive load |
0.5 ms |
Encoder |
Connection of signal encoders |
● for voltage measurement |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.05 % |
Temperature error (relative to input range), (+/-) |
0.005 %/K |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.06 % |
● Current, relative to input area, (+/-) |
0.06 % |
● Resistance thermometer, relative to input area, (+/-) |
0.06 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.04 % |
● Current, relative to input area, (+/-) |
0.04 % |
● Resistance thermometer, relative to input area, (+/-) |
0.04 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
40 dB |
● common mode voltage (USS < 2.5 V) , min. |
70 dB |
Interrupts/diagnostics/status information |
Substitute values connectable |
Yes |
Control technology |
Number of closed-loop controllers |
4 |
Galvanic isolation |
Galvanic isolation controller |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
470 g |
last modified: |