6ES7334-0CE01-0AA0 SIMATIC S7, ANALOG INPUT MODULE

Product Code: 6ES7334-0CE01-0AA0

Availability: In Stock

Price: $231.53
  
 
Artikelnummer 6ES7334-0CE01-0AA0
SIMATIC S7, ANALOG INPUT/OUTPUT SM 334, NON-ISOLATED, 4 AI/2 AO, 1 X 20 PIN, REMOVE AND INSERT WITH BACKPLAIN BUS
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 110 mA
from backplane bus 5 V DC, max. 55 mA
Power losses
Power loss, typ. 3 W
Analog inputs
Number of analog inputs 4
Number of analog inputs for voltage measurement 4
permissible input voltage for voltage input (destruction limit), max. 20 V
permissible input current for current input (destruction limit), max. 40 mA
Cycle time (all channels) max. 5 ms
Input ranges
● Voltage Yes
● Current Yes
● Resistance thermometer No
● Resistance No
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 100 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 50 Ω
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 11 mA
Current output, no-load voltage, max. 15 V
Output ranges, voltage
● 0 to 10 V Yes
Output ranges, current
● 0 to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 5 kΩ
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 300 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 8 bit
Settling time
● for resistive load 0.3 ms
● for capacitive load 3 ms
● for inductive load 0.3 ms
Encoder
Connection of signal encoders
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.9 %
● Current, relative to input area, (+/-) 0.8 %
● Voltage, relative to output area, (+/-) 0.6 %
● Current, relative to output area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.7 %
● Current, relative to input area, (+/-) 0.6 %
● Voltage, relative to output area, (+/-) 0.5 %
● Current, relative to output area, (+/-) 0.5 %
Interrupts/diagnostics/status information
Alarms
● Alarms No
Diagnostic messages
● Diagnostic functions No
Galvanic isolation
Galvanic isolation analog inputs
● between the channels and the backplane bus No
Galvanic isolation analog outputs
● between the channels and the backplane bus No
Isolation
Isolation checked with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 285 g
last modified: 25.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good