SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, 8AI, RESOLUTION 9/12/14 BITS, U/I/THERMOCOUPLE/RESISTANCE INTERRUPT, DIAGNOSTICS; 1X20PIN REMOVE/INSERT W. BACKPLANE BUS |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
200 mA |
from backplane bus 5 V DC, max. |
50 mA |
Power losses |
Power loss, typ. |
1 W |
Analog inputs |
Number of analog inputs |
8 |
Number of analog inputs for resistance measurement |
4 |
permissible input voltage for voltage input (destruction limit), max. |
20 V; continuous; 75 V for max. 1 s (mark to space ratio 1:20) |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
Yes |
● Resistance thermometer |
Yes |
● Resistance |
Yes |
Input ranges (rated values), voltages |
● 0 to +10 V |
No |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
100 kΩ |
● 1 to 10 V |
No |
● -1 V to +1 V |
Yes |
● Input resistance (-1 V to +1 V) |
10 MΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
100 kΩ |
● -2.5 V to +2.5 V |
Yes |
● Input resistance (-2.5 V to +2.5 V) |
100 kΩ |
● -250 mV to +250 mV |
Yes |
● Input resistance (-250 mV to +250 mV) |
10 MΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
100 kΩ |
● -50 mV to +50 mV |
No |
● -500 mV to +500 mV |
Yes |
● Input resistance (-500 mV to +500 mV) |
10 MΩ |
● -80 mV to +80 mV |
Yes |
● Input resistance (-80 mV to +80 mV) |
10 MΩ |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
25 Ω |
● -10 to +10 mA |
Yes |
● Input resistance (-10 to +10 mA) |
25 Ω |
● -20 to +20 mA |
Yes |
● Input resistance (-20 to +20 mA) |
25 Ω |
● -3.2 to +3.2 mA |
Yes |
● Input resistance (-3.2 to +3.2 mA) |
25 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
25 Ω |
Input ranges (rated values), thermoelements |
● Type B |
No |
● Type E |
Yes |
● Input resistance (Type E) |
10 MΩ |
● Type J |
Yes |
● Input resistance (type J) |
10 MΩ |
● Type K |
Yes |
● Input resistance (Type K) |
10 MΩ |
● Type L |
Yes |
● Input resistance (Type L) |
10 MΩ |
● Type N |
Yes |
● Input resistance (Type N) |
10 MΩ |
● Type R |
No |
● Type S |
No |
● Type T |
No |
● Type U |
No |
● Type TXK/TXK(L) to GOST |
No |
Input ranges (rated values), resistance thermometer |
● Cu 10 |
No |
● Ni 100 |
Yes; Standard |
● Input resistance (Ni 100) |
10 MΩ |
● Ni 1000 |
No |
● LG-Ni 1000 |
No |
● Ni 120 |
No |
● Ni 200 |
No |
● Ni 500 |
No |
● Pt 100 |
Yes; Standard |
● Input resistance (Pt 100) |
10 MΩ |
● Pt 1000 |
No |
● Pt 200 |
No |
● Pt 500 |
No |
Input ranges (rated values), resistors |
● 0 to 150 ohms |
Yes |
● Input resistance (0 to 150 ohms) |
10 MΩ |
● 0 to 300 ohms |
Yes |
● Input resistance (0 to 300 ohms) |
10 MΩ |
● 0 to 600 ohms |
Yes |
● Input resistance (0 to 600 ohms) |
10 MΩ |
● 0 to 6000 ohms |
No |
Thermocouple (TC) |
Temperature compensation |
— Parameterizable |
Yes |
— internal temperature compensation |
Yes |
— external temperature compensation with compensations socket |
Yes |
Characteristic linearization |
● Parameterizable |
Yes |
— for thermocouples |
Type E, J, K, L, N |
— for resistance thermometer |
Pt100 (standard, climatic range), Ni100 (standard, climatic range) |
Cable length |
● Cable length, shielded, max. |
200 m; 50 m at 80 mV and thermocouples |
Analog value creation |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
15 bit; Unipolar: 9/12/12/14 bits; bipolar: 9 bits + sign/12 bits + sign/12 bits + sign/14 bits + sign |
● Integration time, parameterizable |
Yes; 2,5 / 16,67 / 20 / 100 ms |
● Basic conversion time, ms |
3 / 17 / 22 /102 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 / 10 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
● for resistance measurement with two-wire connection |
Yes |
● for resistance measurement with three-wire connection |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
1 %; +/-1% (80 mV); +/-0.6% (250 to 1000 mV); +/-0.8% (2.5 to 10 V) |
● Current, relative to input area, (+/-) |
0.7 %; From 3.2 to 20 mA |
● Resistance, relative to input area, (+/-) |
0.7 %; 150, 300, 600 Ohm |
● Resistance thermometer, relative to input area, (+/-) |
0.7 %; +/-0.7% (Pt100/ Ni100); +/-0.8% (Pt100 climate) |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.6 %; +/-0.4% (250 to 1000 mV); +/-0.6 % (2.5 to 10 mV); +/-0.7 % (80 mV) |
● Current, relative to input area, (+/-) |
0.5 %; 3.2 to 20 mA |
● Resistance, relative to input area, (+/-) |
0.5 %; 150, 300, 600 Ohm |
● Resistance thermometer, relative to input area, (+/-) |
0.6 %; +/-0.5% (Pt100/ Ni100); +/-0.6% (Pt100 climate) |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable, channels 0 and 2 |
● Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostic functions |
Yes; Parameterizable |
● Diagnostic information readable |
Yes |
● Diagnostics |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
250 g |
last modified: |