6ES7336-1HE00-0AB0 SIMATIC S7, ANALOG INPUT

Product Code: 6ES7336-1HE00-0AB0

Availability: In Stock

Price: $866.53
  
 
Artikelnummer 6ES7336-1HE00-0AB0
SIMATIC S7, ANALOG INPUT SM336, 6 AI; 14 BIT; 40 PIN, FAILSAFE ANALOG INPUTS FOR SIMATIC S7F SYSTEMS WITH DIAGNOST. INTERRUPT
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from backplane bus 5 V DC, max. 90 mA
from supply voltage L+, max. 160 mA; Typical
Power losses
Power loss, typ. 4.25 W
Analog inputs
Number of analog inputs 6
Number of analog inputs for voltage measurement 4
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
● Voltage Yes
● Current Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) 59 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 107 Ω
● 4 to 20 mA Yes
● Input resistance (4 to 20 mA) 107 Ω
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 14 bit
● Integration time, ms 20 ms (at 50 Hz); 16.66 ms (at 60 Hz)
● Interference voltage suppression for interference frequency f1 in Hz 38 dB
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
Errors/accuracies
Operational limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.48 %
● Current, relative to input area, (+/-) 0.48 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.4 %
● Current, relative to input area, (+/-) 0.4 %
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
Diagnostics indication LED
● Fail-safe operation Yes
● Group error SF (red) Yes
● Monitoring 24 V voltage supply ON (green) Yes; Encoder supply
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the power supply of the electronics Yes; only if sensors are externally supplied
Isolation
Isolation checked with 500V DC/350V AC
Standards, approvals, certificates
Highest safety class achievable in safety mode
● acc. to DIN V 19250 AK 6
● acc. to EN 954 Cat. 4
● acc. to IEC 61508 SIL 3
Connection method
required front connector 40-pin
Dimensions
Width 80 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 480 g
last modified: 08.09.2014