6ES7315-2FH10-0AB0 CPU315F-2 PN/DP, 192KB

Product Code: 6ES7315-2FH10-0AB0

Availability: In Stock

Price: $1,436.45
  
 
Artikelnummer 6ES7315-2FH10-0AB0
General information
Hardware product version 01
Firmware version V2.3.3
Engineering with
● Programming package STEP 7 V5.3 SP3
Supply voltage
Rated value (DC) 24 V
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
external protection for power supply lines (recommendation) 2 A min.
Input current
Current consumption (in no-load operation), typ. 100 mA
Rated value at 24 V DC 100 mA; idling
Inrush current, max. 2.5 A; Typical
Inrush current, typ. 2.5 A
I²t 1 A²·s
Power loss
Power loss, typ. 3.5 W
Memory
Work memory
● integrated 192 kbyte
● expandable No
Load memory
● Plug-in (MMC) Yes
● Plug-in (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
● expandable FEPROM can be plugged in as MMC
Backup
● present Yes; maintenance-free
CPU processing times
for bit operations, typ. 0.1 µs
for bit operations, max. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
CPU-blocks
Number of blocks (total) 1 024
DB
● Number, max. 1 023; From DB 1 to DB 1023
● Size, max. 16 kbyte
FB
● Number, max. 2 048; from FB 0 to FB 2047
● Size, max. 16 kbyte
FC
● Number, max. 2 048; from FC 0 to FC 2047
● Size, max. 16 kbyte
OB
● Number, max. see instruction list
● Size, max. 16 kbyte
● Number of free cycle OBs 1; OB 1
● Number of time alarm OBs 1; OB 10
● Number of delay alarm OBs 1; OB 20
● Number of time interrupt OBs 1; OB 35
● Number of process alarm OBs 1; OB 40
● Number of startup OBs 1; OB 100
● Number of asynchronous error OBs 1; OB 80
● Number of synchronous error OBs 2; OB 121, 122
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
of which retentive without battery
— adjustable Yes
— preset Z 0 to Z 7
Retentivity
— adjustable Yes
Counting range
— adjustable Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
● Number 256
Retentivity
— adjustable Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area, total up to 128 KB
Flag
● Number, max. 2 048 byte
● Retentivity available Yes; MB 0 to MB 2047
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 1 023; from DB 1 to DB 1024
● Size, max. 16 kbyte
Local data
● per priority class, max. 1 024 byte; max. 510 bytes per block
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
of which distributed
— Inputs 2 kbyte
— Outputs 2 kbyte
Process image
● Inputs 384 byte
● Outputs 384 byte
Digital channels
● Inputs 16 384
● Outputs 16 384
● Inputs, of which central 1 024; max.
● Outputs, of which central 1 024; max.
Analog channels
● Inputs 1 024
● Outputs 1 024
● Inputs, of which central 256
● Outputs, of which central 256
Hardware configuration
Number of DP masters
● integrated 1
● via CP 4
Number of operable FMs and CPs (recommended)
● FM 8
● CP, point-to-point 8
● CP, LAN 10
Rack
● Racks, max. 4
● Modules per rack, max. 8
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk; At 40 °C ambient temperature
Operating hours counter
● Number 1
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● in AS, master Yes
● in AS, slave Yes
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
isolated Yes
Power supply to interface (15 to 30 V DC), max. 200 mA
Functionality
● MPI Yes
● DP master Yes
● DP slave Yes
● Point-to-point connection No
MPI
● Number of connections 16
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
DP master
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 124
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— DPV1 Yes
DP slave
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32; With max. 32 bytes each
Services
— Routing Yes; Only with active interface
— Global data communication No
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
2. Interface
Interface type PROFINET
Physics Ethernet
isolated Yes
Power supply to interface (15 to 30 V DC), max. 0 mA
automatic detection of transmission rate Yes; 10/100 Mbit/s
Functionality
● MPI No
● DP master No
● DP slave No
● PROFINET IO Controller Yes
● PROFINET CBA Yes
● Point-to-point connection No
PROFINET IO Controller
● Transmission rate, max. 100 Mbit/s
● Number of connectable IO Devices, max. 128
● Updating time 1 to 512 ms (minimum value depends on communication share set for PROFINET I/O, on the number of I/O devices, and on the volume of configured user data)
Services
— PG/OP communication Yes
— Routing Yes
— S7 communication Yes; with loadable FBs, max. configurable connections: 16
— Open IE communication Yes; via TCP/IP
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
— User data consistency, max. 256 byte
PROFINET CBA
● acyclic transmission Yes
● cyclic transmission Yes
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD loops, max. 8
● Number of GD packets, max. 8
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 8
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● as client Yes; via integrated PROFINET interface and loadable FB or via CP and loadable FB
S5 compatible communication
● supported Yes; Via CP and loadable FB
Open IE communication
● TCP/IP Yes; via integrated PROFINET interface and loadable FBs
— Number of connections, max. 8
— Data length, max. 1 460 byte
PROFINET CBA (at set setpoint communication load)
● Setpoint for the CPU communication load 50 %
● Number of remote interconnection partners 32
● Number of functions, master/slave 17
● Total of all master/slave connections 1 000
● Data length of all incoming connections master/slave, max. 4 000 byte
● Data length of all outgoing connections master/slave, max. 4 000 byte
● Number of device-internal and PROFIBUS interconnections 500
● Data length of device-internal und PROFIBUS interconnections, max. 4 000 byte
● Data length per connection, max. 1 400 byte
Remote interconnections with acyclic transmission
— Sampling frequency: Sampling time, min. 500 ms
— Number of incoming interconnections 100
— Number of outgoing interconnections 100
— Data length of all incoming interconnections, max. 2 000 byte
— Data length of all outgoing interconnections, max. 2 000 byte
— Data length per connection, max. 1 400 byte
Remote interconnections with cyclic transmission
— Transmission frequency: Transmission interval, min. 10 ms
— Number of incoming interconnections 200
— Number of outgoing interconnections 200
— Data length of all incoming interconnections, max. 2 000 byte
— Data length of all outgoing interconnections, max. 2 000 byte
— Data length per connection, max. 450 byte
HMI variables via PROFINET (acyclic)
— Number of stations that can log on for HMI variables (PN OPC/iMap) 3; 2x PN OPC/1x iMap
— HMI variable updating 500 ms
— Number of HMI variables 200
— Data length of all HMI variables, max. 2 000 byte
PROFIBUS proxy functionality
— supported Yes
— Number of linked PROFIBUS devices 16
— Data length per connection, max. 240 byte; Slave-dependent
Number of connections
● overall 16
● usable for PG communication 15; max.
— reserved for PG communication 1
— adjustable for PG communication, min. 1
— adjustable for PG communication, max. 15; 1 to 15
● usable for OP communication 15
— reserved for OP communication 1
— adjustable for OP communication, min. 1
— adjustable for OP communication, max. 15; 1 to 15
● usable for S7 basic communication 14
— reserved for S7 basic communication 0
— adjustable for S7 basic communication, min. 0
— adjustable for S7 basic communication, max. 14; 0 to 14
S7 message functions
Number of login stations for message functions, max. 16; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Forcing, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— adjustable No
Configuration
Configuration software
● STEP 7 Yes; with HSP88, otherwise with SP3
Programming
● Command set see instruction list
● Nesting levels 8
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 80 mm
Height 125 mm
Depth 130 mm