6ES7151-7AA10-0AB0 ET200S, IM151-7 CPU, 48KB

Product Code: 6ES7151-7AA10-0AB0

Availability: In Stock

Price: $506.90
  
 
Artikelnummer 6ES7151-7AA10-0AB0
General information
Hardware product version 02
Firmware version V2.1.0
Engineering with
● Programming package 1) STEP 7 V5.1 + SP6 or higher, optional: -S7SCL, -S7-GRAPH; 2) STEP 7 V5.2 + SP1 or higher (for IM 151-7 CPU with DP master module)
Input current
from supply voltage 1L+, max. 280 mA with DP master module
Memory
Work memory
● integrated approx. 16 K instructions
Backup
● present Guaranteed by MMC (maintenance-free)
CPU-blocks
Number of blocks (total) FCs + FBs + DBs
OB
● Number, max. see instruction list
Counters, timers and their retentivity
S7 counter
Retentivity
— preset Z 0 to Z 7
IEC counter
● Type SFB
● Number Unlimited (limited only by RAM capacity)
S7 times
Retentivity
— preset No times retentive
IEC timer
● Type SFB
● Number Unlimited (limited only by RAM capacity)
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. all
Flag
● Retentivity preset MB 0 to MB 15
● Number of clock memories 1 memory byte
Data blocks
● Number, max. DB 0 reserved
Address area
Process image
● Inputs Not adjustable
● Outputs Not adjustable
Time of day
Clock
● Backup time At 40 °C ambient temperature, typically
Operating hours counter
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Must be restarted at each restart
1. Interface
Interface type Integrated RS 485 interface
Physics RS 485
Functionality
● DP slave active / passive
MPI
● Number of connections Notice: 12 connections per CPU, not per interface
Services
— Routing With master module
DP slave
● Number of connections Notice: 12 connections per CPU, not per interface
● GSD file http://www.ad.siemens.de/csi_e/gsd
● automatic baud rate search only with passive interface
● User data per address area, max. Up to max. size of the transfer memory
Services
— Routing Only when interface active and in master mode
2. Interface
Interface type External interface via master module 6ES7138-4HA00-0AB0
Physics RS 485
Power supply to interface (15 to 30 V DC), max. No
DP master
● Number of connections, max. Notice: 12 connections per CPU, not per interface
● Number of DP slaves, max. Per station
Communication functions
S7 basic communication
● User data per job (of which consistent), max. 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
Number of connections
● usable for routing As slave only with active interface, with IM 151-7 CPU as DP master
S7 message functions
Number of login stations for message functions, max. Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages ALARM_S, ALARM_SC, ALARM_SQ
Test commissioning functions
Status/control
● Variables Inputs, outputs, memory bits, DB, times, counters
Forcing
● Forcing, variables Inputs, outputs
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation tested with 500 V DC
Configuration
Configuration rules max. 63 peripheral modules per station; station width < 1 m or < 2 m; max. 10 A per load group (power module); master interface module on right next to IM 151-7 CPU (X2 interface)
Programming
● Command set see instruction list
● System functions (SFC) see instruction list
● System function blocks (SFB) see instruction list
Programming language
— SCL Optional
— GRAPH Optional
Dimensions
Width DP master module: 35 mm
Weights
Weight, approx. DP master module: Approx. 100 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: