6ES7151-7AA20-0AB0 ET200S, IM151-7 CPU INTERFACE, 96KB

Product Code: 6ES7151-7AA20-0AB0

Availability: In Stock

Price: $349.35
  
 
Artikelnummer 6ES7151-7AA20-0AB0
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
● short-circuit protection Yes
● Reverse polarity protection Yes
Input current
from supply voltage 1L+, max. 250 mA
Output current
Current output to backplane bus (DC 5 V), max. 700 mA
Power losses
Power loss, typ. 3.3 W
Memory
Work memory
● Integrated 96 kbyte
● expandable No
Load memory
● pluggable (MMC) Yes
● pluggable (MMC), max. 8 Mbyte
● Data management on MMC (after last programming), min. 10 y
Backup
● present Yes
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1 024
DB
● Number, max. 511
● Size, max. 16 kbyte
FB
● Number, max. 1 024
● Size, max. 16 kbyte
FC
● Number, max. 1 024
● Size, max. 16 kbyte
OB
● Size, max. 16 kbyte
● Number of free cycle OBs 1
● Number of time alarm OBs 1
● Number of delay alarm OBs 1
● Number of time interrupt OBs 1
● Number of process alarm OBs 1
● Number of DPV1 alarm OBs 3
● Number of startup OBs 1
● Number of asynchronous error OBs 6
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
Counting range
— can be set Yes
— lower limit 0
— upper limit 999
IEC counter
● present Yes
S7 times
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. 64 kbyte
Flag
● Number, max. 256 byte
● Retentivity available Yes
● Number of clock memories 8
Data blocks
● Number, max. 511
● Size, max. 16 kbyte
Local data
● per priority class, max. 510 byte
Address area
I/O address area
● Inputs 2 048 byte
● Outputs 2 048 byte
Process image
● Inputs 128 byte
● Outputs 128 byte
Digital channels
● Inputs 16 336
● Outputs 16 336
● Inputs, of which central 248
● Outputs, of which central 248
Analog channels
● Inputs 1 021
● Outputs 1 021
● Inputs, of which central 124
● Outputs, of which central 124
Hardware configuration
Number of modules per system, max. 63
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Deviation per day, max. 10 s
● Backup time 6 wk
Operating hours counter
● Number 1
● retentive Yes
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes
● to DP, slave Yes
● in AS, master No
● in AS, slave No
Interfaces
Number of USB interfaces 0
Number of parallel interfaces 0
Number of other interfaces 0
PROFINET IO
● Number of PROFINET interfaces 0
WLAN
● Number of wireless interfaces 0
1st interface
Isolated Yes
Power supply to interface (15 to 30 V DC), max. 80 mA
Functionality
● MPI Yes
● DP master No
● DP slave Yes
● Point-to-point connection No
MPI
● Number of connections 12
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
DP slave
● Number of connections 12
● Transmission rate, max. 12 Mbit/s
● Automatic baud rate search Yes
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— Routing Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
2nd interface
Isolated Yes
Functionality
● MPI No
● DP master Yes
● Point-to-point connection No
DP master
● Number of connections, max. 12
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication No
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as client No
— S7 communication, as server Yes
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
— DPV1 Yes
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD packets, max. 4
● Number of GD packets, transmitter, max. 4
● Number of GD packets, receiver, max. 4
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte
S7 communication
● supported Yes
● as server Yes
● As client No
● User data per job, max. 180 byte
● User data per job (of which consistent), max. 64 byte
S5-compatible communication
● supported No
Standard communication (FMS)
● supported No
Number of connections
● overall 12
● usable for PG communication 11
— reserved for PG communication 1
— Adjustable for PG communication, max. 11
● usable for OP communication 11
— reserved for OP communication 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication 10
— Reserved for S7 basic communication 0
— adjustable for S7 basic communication, max. 10
● usable for routing 4
S7 message functions
Number of login stations for message functions, max. 12
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— can be set No
Galvanic isolation
between load voltage and all other switching components Yes
between PROFIBUS DP and all other circuit components Yes
Configuration
Configuration software
● STEP 7 Yes
programming
● Nesting levels 8
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— GRAPH Yes
Know-how protection
● User program protection/password protection Yes
Cycle time monitoring
● lower limit 1 ms
● upper limit 6 000 ms
● can be set Yes
● preset 150 ms
Dimensions
Width 60 mm
Height 119.5 mm
Depth 75 mm
Weights
Weight, approx. 200 g