6ES7147-2AA01-0XB0 ET200X: BM 147-2 CPU

Product Code: 6ES7147-2AA01-0XB0

Availability: In Stock

Price: $1,056.27
  
 
Basic module BM 147 CPU for ET 200X

-
SIMATIC DP, BASIC MODULE ET200X: BM147-2 CPU, 64KB WORK MEMORY FOR PREPROCESSING WITH INT. PLC FUNCTIONS, INT.PROFIBUS DP SLAVE IF WITH ADD. PROFIBUS DP MASTER IF, PROT. IP65/67
Supply voltage
Load voltage 1L+
Rated value (DC) 24 V; Permissible range: 20.4 to 28.8 V
Short-circuit protection Yes; internal (thermally reversible); no for looping through
Reverse polarity protection No
Load voltage 2L+
Rated value (DC) 24 V; Permissible range: 20.4 to 28.8 V
Reverse polarity protection No
Power losses
Power loss, typ. 3 W
Memory
Work memory
integrated 64 kbyte; 21 K instructions
expandable No
Load memory
expandable FEPROM, max. 8 Mbyte; can be plugged in as MMC
Backup
present Yes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1024; DBs, FCs, FBs
DB
Number, max. 511
Size, max. 16 kbyte
FB
Number, max. 512; In number range from FB 0 to FB 2047
Size, max. 16 kbyte
FC
Number, max. 512; In number band of FC0 to FC2047
Size, max. 16 kbyte
OB
Description see instruction list
Size, max. 16 kbyte
Nesting depth
per priority class 8
additional within an error OB 4
Counters, timers and their retentivity
S7 counter
Number 256
Retentivity
adjustable Yes
preset Z 0 to Z 7
Counting range
lower limit 0
upper limit 999
IEC counter
present Yes; Number unlimited (limited only by work memory)
Type SFB
S7 times
Number 256
Retentivity
adjustable Yes
preset No retentivity
Time range
lower limit 10 ms
upper limit 9990 s
IEC timer
present Yes; Number unlimited (limited only by work memory)
Type SFB
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. all
Flag
Number, max. 256 byte
Retentivity available Yes
Retentivity preset MB 0 to MB 15
Number of clock memories 8; 1 memory byte
Local data
per priority class, max. 510 byte
Address area
I/O address area
Inputs 1 kbyte
Outputs 1 kbyte
Process image
Inputs 128 byte
Outputs 128 byte
Digital channels
Inputs 8192 bits
Outputs 8192 bits
Inputs, of which central 56 bytes
Outputs, of which central 56 bytes
Analog channels
Inputs 512 words
Outputs 512 words
Inputs, of which central 14 words
Outputs, of which central 14 words
Hardware configuration
Expansion modules
Number of expansion modules, max. 7
of which motor starters/frequency converters, max. 6
of which, pneumatic interfaces, max. 6
Time of day
Clock
Hardware clock (real-time clock) Yes
battery-backed and synchronizable Yes; Backup time typically 6 weeks (at 40 °C ambient temperature)
Deviation per day, max. 10 s
Operating hours counter
Number 1
Number/Number range 0
Range of values 0 to 2^31 hours (when using SFC 101)
Granularity 1 hour
retentive Yes; Must be restarted at each restart
Clock synchronization
supported Yes
to MPI, slave Yes
in AS, master Yes
in AS, slave Yes
1st interface
Type of interface Coexistent, integrated RS 485 interface
Physics RS 485
Isolated Yes
Functionality
MPI Yes
DP master Yes
DP slave Yes; active / passive
Point-to-point connection No
MPI
Transmission rate, max. 12 Mbit/s
Services
PG/OP communication Yes
Routing Yes
Global data communication Yes
S7 basic communication Yes
S7 communication Yes
S7 communication, as server Yes
DP master
Services
PG/OP communication Yes
Routing Yes
Global data communication No
S7 basic communication No
S7 communication Yes
S7 communication, as server Yes
Equidistance mode support Yes
SYNC/FREEZE Yes
Activation/deactivation of DP slaves Yes
Direct data exchange (slave-to-slave communication) Yes
DPV1 Yes
Address area
Inputs, max. 1 kbyte
Outputs, max. 1 kbyte
User data per DP slave
User data per DP slave, max. 244 byte; 244 bytes/244 bytes
DP slave
Number of connections 12
Transmission rate, max. 12 Mbit/s
Address area, max. 32
User data per address area, max. 32 byte
Services
Routing Yes; with interface active
S7 communication, as client No
S7 communication, as server No
Transfer memory
Inputs 244 byte
Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
supported Yes
Number of GD packets, max. 4
Number of GD packets, transmitter, max. 4
Number of GD packets, receiver, max. 4
Size of GD packets, max. 22 byte
Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
supported Yes
User data per job, max. 76 byte
User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
supported Yes
as server Yes
as client No
User data per job, max. 180 byte; With PUT/GET
User data per job (of which consistent), max. 64 byte
S5-compatible communication
supported No
Number of connections
overall 12
usable for PG communication
reserved for PG communication 1
Adjustable for PG communication, max. 11
usable for OP communication
reserved for OP communication 1
adjustable for OP communication, max. 11
usable for S7 basic communication
Reserved for S7 basic communication 10
adjustable for S7 basic communication, max. 11
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
Status/control variable Yes
Variables Inputs, outputs, memory bits, DB, times, counters
Number of variables, max. 30
of which status variables, max. 30
of which control variables, max. 14
Forcing
Forcing Yes
Force, variables Inputs, outputs
Number of variables, max. 10
Diagnostic buffer
present Yes
Number of entries, max. 100
adjustable No
Configuration
Configuration software
STEP 7 Yes; V5.2 SP1
Dimensions
Width 175 mm
Height 110 mm
Depth 90 mm
Status Jan 23, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good