Supply voltage
Input voltage acc. to VDE
permissible range, lower limit (AC) 340 V
permissible range, upper limit (AC) 500 V
Input voltage acc. to UL
permissible range, lower limit (AC) 480 V
permissible range, upper limit (AC) 340 V
Line frequency
permissible frequency range, lower limit 47 Hz
permissible frequency range, upper limit 63 Hz
Mains filter
integrated Yes; Type A (to EN 55011)
Class A Yes; to EN 55011
Operations for mains buffering time (20 ms)
Max. current for Ue < 380 V 1.85 A; at 3.8 A approx. 8 ms
Max. current for Ue >= 380 V 2.1 A; at 3.8 A approx. 8 ms
Input current
Continuous current on continued looping of the supply voltage, max. 16 A
from load voltage L+ (without load), max. 125 mA
from backplane bus 5 V DC, typ. 50 mA
Output current
Continuous output current at 40 °C
at 2 kHz and 4 kHz, max. 3.8 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 8 kHz, max. 3 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 16 kHz, max. 1.45 A
Continuous output current at 55 °C
at 2 kHz and 4 kHz, max. 2.1 A; Continuous currents > 1.9 A are only permissible if at least one of the following conditions is met: - Ambient temperature < 50 °C - Input continuous current when looping through the load supply voltage < 8 A
at 8 kHz, max. 1.7 A
at 16 kHz, max. 1.05 A
Power
Degree of efficiency of the converter, typ. 97 %
Power losses
in intermittent operation, max. 70 W
in continuous operation, max. 42 W
Interrupts/diagnostics/status information
Alarms
Diagnostic alarm Yes
Diagnostic messages
Diagnostics Yes
Diagnostics indication LED
Group error SF (red) Yes
Status indicator STAT (yellow) Yes
Monitoring the power supply, power module PWR (green) Yes
Drive technology
Motor output, cable length max. 10 m
Overload capability 150 %; for 60 s, relative to rated current
Output frequency, min. 0 Hz
Output frequency, max. 300 Hz
Output frequency, resolution 0.01 Hz
Control/mode
V/f characteristic Yes
four quadrants Yes
Motor
Power factor (cos phi), min. 0.7
Number of poles 2, 4 or 6
Motor brake AC (rated voltage according to infeed supply voltage) / max. 1 A
short-circuit proof No; internal fuse 4 A provided
Thermistor Response range about 4 to 5 kohms; channel-related error message: overload
Rated motor power at 3 x 400 V AC
acc. to VDE, max. 1.5 kW
acc. to UL, max. 2 hp
Galvanic isolation
between the load voltages Yes
between load voltage and all other switching components Yes
Permissible potential difference
between different circuits 1500 V AC
Isolation
Isolation checked with 2830 V DC
Degree and class of protection
Protection against Overtemperature in the converter; overtemperature in the motor; overvoltage and undervoltage; short-circuit and ground fault protection; motor stalling protection, no-load protection (interrupt)
Dimensions
Width 120 mm
Height 265 mm
Depth 181 mm
Weights
Weight, approx. 3 kg