6ES7142-4BD00-0AB0 ET200PRO, EM 4DO 24VDC/2.0A HF

Product Code: 6ES7142-4BD00-0AB0

Availability: In Stock

Price: $71.93
  
 
Digital electronic modules 8DI and 4DQ

-
SIMATIC DP, ELECTRONIC MODULES FOR ET200PRO 4 DO DC 24V, 2.0A HIGH FEATURE, CHANNEL DIAGNOSTICS; SHORT CIRCUIT AND WIRE BREAK; INCLUSIVE BUS MODULE CONNECTING MODULE IO 6ES7194-4..00-0AA0 MUST BE ORDERED SEPERATELY
FH technology
Module for failsafe applications No
Supply voltage
Load voltage 2L+
Rated value (DC) 24 V
short-circuit protection Yes; per channel, electronic
Reverse polarity protection Yes; against destruction; load increasing
Input current
from load voltage 2L+ (without load), max. 40 mA
from backplane bus 3.3 V DC, max. 40 mA
Power losses
Power loss, typ. 2.5 W
Address area
Address space per module
with packing 4 bit
without packing 1 byte
Digital outputs
Number of digital outputs 4
Short-circuit protection Yes
Response threshold, typ. 3
Limitation of inductive shutdown voltage to 2L+ (-47 V)
Controlling a digital input Yes
Switching capacity of the outputs
Lamp load, max. 10 W
Load resistance range
lower limit 12 Ω
upper limit 4 kΩ
Output voltage
for signal "1", min. 2L+ (-0,8 V)
Output current
for signal "1" rated value 2 A
for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
for increased power No
for redundant control of a load Yes
Switching frequency
with resistive load, max. 100 Hz
with inductive load, max. 0.5 Hz
on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
all mounting positions
up to 55 °C, max. 4 A
Cable length
Cable length, shielded, max. 30 m
Cable length unshielded, max. 30 m
Interrupts/diagnostics/status information
Substitute values connectable Yes
Alarms
Diagnostic alarm Yes
Diagnostic messages
Diagnostic functions Yes
Diagnostic information readable Yes
Wire break Yes
Short circuit Yes
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital output (green) Yes
Channel error indicator F (red) Yes
Parameter
Diagnosis: wire break channel by channel
Diagnosis: short circuit channel by channel
Behavior on CPU/Master STOP channel by channel
Galvanic isolation
between backplane bus and all other circuit components Yes
between the channels and backplane bus Yes
Galvanic isolation digital outputs
between the channels No
between the channels and the backplane bus Yes
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 45 mm
Height 130 mm
Depth 35 mm; without terminal module
Weights
Weight, approx. 140 g
Status Jun 16, 2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: