6ES7147-1AA11-0XB0 ET200X, BM147/CPU, WITH SPS-FUNCTION

Product Code: 6ES7147-1AA11-0XB0

Availability: In Stock

Price: $656.23
  
 
Artikelnummer 6ES7147-1AA11-0XB0
SIMATIC DP, BASIC MODULE ET200X: BM147-1 CPU, 64KB WORK MEMORY FOR PREPROCESSING WITH INT. PLC FUNCTIONS, INT.PROFIBUS DP SLAVE IF, PROT. IP65/67
Supply voltage
Load voltage 1L+
● Rated value (DC) 24 V; Permissible range: 20.4V to 28.8V
● short-circuit protection Yes
● Reverse polarity protection No
Load voltage 2L+
● Rated value (DC) 24 V; Permissible range: 20.4V to 28.8V
● Reverse polarity protection No
Power losses
Power loss, typ. 3 W
Memory
Work memory
● Integrated 64 kbyte; 21 K instructions
● expandable No
Load memory
● expandable FEPROM, max. 8 Mbyte; can be plugged in as MMC
Backup
● present Yes; Guaranteed by MMC (maintenance-free)
CPU processing times
for bit operations, typ. 0.1 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 2 µs
for floating point arithmetic, typ. 3 µs
CPU-blocks
Number of blocks (total) 1 024; DBs, FCs, FBs
DB
● Number, max. 511
● Size, max. 16 kbyte
FB
● Number, max. 512; In number range from FB 0 to FB 2047
● Size, max. 16 kbyte
FC
● Number, max. 512; In number band of FC0 to FC2047
● Size, max. 16 kbyte
OB
● Description see instruction list
● Size, max. 16 kbyte
Nesting depth
● per priority class 8
● additional within an error OB 4
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— can be set Yes
— preset Z 0 to Z 7
Counting range
— lower limit 0
— upper limit 999
IEC counter
● present Yes; Number unlimited (limited only by work memory)
● Type SFB
S7 times
● Number 256
Retentivity
— can be set Yes
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes; Number unlimited (limited only by work memory)
● Type SFB
Data areas and their retentivity
retentive data area in total (incl. times, counters, flags), max. all
Flag
● Number, max. 256 byte
● Retentivity available Yes
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Local data
● per priority class, max. 510 byte
Address area
I/O address area
● Inputs 1 kbyte
● Outputs 1 kbyte
Process image
● Inputs 128 byte
● Outputs 128 byte
Digital channels
● Inputs 8192 bits
● Outputs 8192 bits
● Inputs, of which central 56 byte
● Outputs, of which central 56 byte
Analog channels
● Inputs 512 words
● Outputs 512 words
● Inputs, of which central 14 words
● Outputs, of which central 14 words
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes; Backup time typically 6 weeks (at 40 °C ambient temperature)
● Deviation per day, max. 10 s
Operating hours counter
● Number 1
● Number/Number range 0
● Range of values 0 to 2^31 hours (when using SFC 101)
● Granularity 1 hour
● retentive Yes; Must be restarted at each restart
Clock synchronization
● supported Yes
● to MPI, slave Yes
● in AS, master Yes
● in AS, slave Yes
1st interface
Interface type Coexistent, integrated RS 485 interface
Physics RS 485
Isolated Yes
Functionality
● MPI Yes
● DP master No
● DP slave Yes; active / passive
● Point-to-point connection No
MPI
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing No
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
— S7 communication, as server Yes
DP slave
● Number of connections 12
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32
● User data per address area, max. 32 byte
Services
— Routing No
— S7 communication, as client No
— S7 communication, as server No
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD packets, max. 4
● Number of GD packets, transmitter, max. 4
● Number of GD packets, receiver, max. 4
● Size of GD packets, max. 22 byte
● Size of GD packet (of which consistent), max. 22 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
● User data per job (of which consistent), max. 76 byte; 76 bytes (with X_SEND or X_RCV); 64 bytes (with X_PUT or X_GET as server)
S7 communication
● supported Yes
● as server Yes
● As client No
● User data per job, max. 180 byte; With PUT/GET
● User data per job (of which consistent), max. 64 byte
S5-compatible communication
● supported No
Number of connections
● overall 12
● usable for PG communication
— reserved for PG communication 1
— Adjustable for PG communication, max. 11
● usable for OP communication
— reserved for OP communication 1
— adjustable for OP communication, max. 11
● usable for S7 basic communication
— Reserved for S7 basic communication 10
— adjustable for S7 basic communication, max. 11
S7 message functions
Number of login stations for message functions, max. 12; Depending on the configured connections for PG/OP and S7 basic communication
Process diagnostic messages Yes
simultaneously active Alarm-S blocks, max. 40
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 2
Status/control
● Status/control variable Yes
● Variables Inputs, outputs, memory bits, DB, times, counters
● Number of variables, max. 30
● of which status variables, max. 30
● of which control variables, max. 14
Forcing
● Forcing Yes
● Force, variables Inputs, outputs
● Number of variables, max. 10
Diagnostic buffer
● present Yes
● Number of entries, max. 100
— can be set No
Configuration
Configuration software
● STEP 7 Yes; V5.2 SP1
Dimensions
Width 175 mm
Height 110 mm
Depth 90 mm
last modified: 25.09.2014