6ES7138-4CF03-0AB0 ET200S, POWERMOD. PM-E F PM, DC24V

Product Code: 6ES7138-4CF03-0AB0

Availability: In Stock

Price: $183.58
  
 
Artikelnummer 6ES7138-4CF03-0AB0
SIMATIC DP, POWER MODULE PM-E F PROFISAFE, FOR ET 200S; 24V DC USEABLE FOR INSTALLATIONS WITH UNGROUNDED REFERENCE POTENTIAL RELAIS FOR FAIL-SAFE SWITCHING OF VOLTAGE BUSES P1 AND P2 UP TO CATEGORY 3 (EN954-1)/ SIL2 (IEC61508)/PLD (ISO13849), 2 FAIL-SAFE DIGITAL OUTPUTS UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/PLE (ISO13849), ALSO USEABLE IN PROFINET-NETWORKS W. IM151-3 HF
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection No
Input current
from load voltage L+ (without load), max. typ. 100 mA
from backplane bus 24 V DC, max. 28 mA
Current carrying capacity
Current carrying capacity up to 40 °C, max. 10 A
Current carrying capacity up to 60 °C, max. 6 A
Power losses
Power loss, typ. 4 W
Address area
Address space per module
● without packing 5 byte; Input and output in each case
Digital inputs
Cable length
● Cable length, shielded, max. 200 m
● Cable length unshielded, max. 200 m
Digital outputs
Number of digital outputs 2
short-circuit protection Yes; Electronic
● Response threshold, typ. Response threshold (short-circuit): 5 to 12 A; response threshold (external short-circuit to ground): 5 to 12 A; response threshold (external short-circuit to P potential): 25 to 45 A
Limitation of inductive shutdown voltage to L+ (-2x 47 V)
Controlling a digital input No
Switching capacity of the outputs
● Lamp load, max. 10 W
Load resistance range
● lower limit 12 Ω
● upper limit 1 kΩ
Output voltage
● for signal "1", min. L+ (-2,0 V), current sourcing switch: L+ (-1,5 V), voltage drop on current sinking switch: max. 0.5 V
Output current
● for signal "1" rated value 2 A
● for signal "1" permissible range for 0 to 60 °C, min. 20 mA
● for signal "1" permissible range for 0 to 60 °C, max. 2.4 A
● for signal "0" residual current, max. 0.5 mA
Parallel switching of 2 outputs
● for increased power No
● for redundant control of a load No
Switching frequency
● with resistive load, max. 30 Hz
● with inductive load, max. 0.1 Hz
● on lamp load, max. 10 Hz
Aggregate current of outputs (per group)
horizontal installation
— up to 40 °C, max. 10 A
— up to 55 °C, max. 7 A
— up to 60 °C, max. 6 A
vertical installation
— up to 40 °C, max. 6 A
Relay outputs
Switching capacity of contacts
— at ohmic load, up to 50 °C, max. 10 A
Cable length
● Cable length, shielded, max. 200 m
● Cable length unshielded, max. 200 m
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Diagnostics Yes
● Wire break Yes
● Short circuit Yes
● Missing load voltage Yes
Diagnostics indication LED
● Rated load voltage PWR (green) Yes
● Group error SF (red) Yes
● Status indicator digital output (green) Yes
Galvanic isolation
Galvanic isolation digital outputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ No
Isolation
Isolation checked with 500 V DC
tested with
● Channels against backplane bus and load voltage L+ 500 V DC
Standards, approvals, certificates
Highest safety class achievable in safety mode
● acc. to EN 954 4
● acc. to IEC 61508 Up to SIL 3
Dimensions
Width 30 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 88 g
last modified: 25.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good