6ES7135-0HF01-0XB0 ET200B, EL-MOD., 4AO, 0/4-20MA, +/-10V

Product Code: 6ES7135-0HF01-0XB0

Availability: In Stock

Price: $646.64
  
 
Artikelnummer 6ES7135-0HF01-0XB0
SIMATIC DP, ELECTRONIC MODULE ANALOG, FOR ET 200B, W=160MM, 4AO 0(4)...20MA; +/- 10V, 11 BIT, 12 MBIT/S
Supply voltage
permissible range, lower limit (DC) 18.5 V
permissible range, upper limit (DC) 30.2 V
Load voltage 1L+
● Rated value (DC) 24 V; Value at t < 0.5 s: 35 V
Input current
from supply voltage L+, max. 200 mA; Logic
Power losses
Power loss, typ. 2.4 W
Hardware configuration
Rack
● Required terminal block TB8
Analog outputs
Number of analog outputs 4
Voltage output, short-circuit protection Yes; Electronic; max. 1 output in parallel
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
● 0 to 10 V Yes
● -10 to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● 4 to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with current outputs, max. 300 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● Cable length, shielded, max. 100 m
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 11 bit; Two''s complement
● Conversion time (per channel) 1 ms
Settling time
● for resistive load 0.1 ms
● for capacitive load 3.3 ms
● for inductive load 0.5 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-) 0.05 %
Linearity error (relative to output range), (+/-) 0.05 %
Temperature error (relative to output range), (+/-) 0.02 %/K
Crosstalk between the outputs, min. 40 dB
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) 0.05 %
Operational limit in overall temperature range
● Voltage, relative to output area, (+/-) 0.05 %
● Current, relative to output area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output area, (+/-) 0.2 %
● Current, relative to output area, (+/-) 0.3 %
Interfaces
PROFIBUS DP
● Transmission rate, max. 12 Mbit/s
Communication functions
Bus protocol/transmission protocol PROFIBUS DP
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostics indication LED
● Bus fault BF (red) Yes
● Run mode RUN (green) Yes
Galvanic isolation
between electronic block and PROFIBUS DP Yes
Galvanic isolation analog outputs
● Galvanic isolation analog outputs No
Degree and class of protection
IP20 Yes
Ambient conditions
Operating temperature
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C; 40°C for other mountings
Air pressure
● permissible range, min. 795 hPa
● permissible range, max. 1 080 hPa
Relative humidity
● Operation, min. 15 %
● Operation, max. 95 %; RH class 2 in accordance with IEC 1131-2
Vibrations
● Operation, checked according to IEC 60068-2-6 Yes; IEC 68, Part 2-6; 10 to 57 Hz; (constant amplitude 0.075 mm); 57 to 150 Hz; (constant acceleration 1 g)
Shock test
● checked according to IEC 60068-2-27 Yes; IEC 68, Part 2-27; half-sine, 15 g, 11 ms
Connection method
Inputs/outputs Screw-type and spring-loaded terminals, permanent wiring; 3 and 4-wire connection
Dimensions
Width 160 mm; EB and TB
Height 130 mm; EB and TB
Depth 60 mm; EB and TB
Weights
Weight, approx. 550 g; EB and TB
last modified: 08.09.2014