6ES7135-4GB52-0AB0 ET200S, EL-MOD., 2AO I, +/-20MA, 4-20MA

Product Code: 6ES7135-4GB52-0AB0

Availability: In Stock

Price: $169.88
  
 
Artikelnummer 6ES7135-4GB52-0AB0
SIMATIC DP, ELECTRONIC MODULE FOR ET 200S, 2 AO I HIGH SPEED 15 MM WIDE, +/-20 MA; 16 BIT, 4 . .20 MA; 16 BIT CYCLE TIME 0.1 MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 150 mA; With load
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, max. 2.4 W; Typical
Address area
Address space per module
● Address space per module, max. 4 byte
Analog outputs
Number of analog outputs 2
Current output, no-load voltage, max. 18 V
Cycle time (all channels) max. 250 µs
Output ranges, current
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Connection of actuators
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH; for TWA 100µs
Destruction limits against externally applied voltages and currents
● Current, max. 15 mA; Max. 15 V / 5 hours (higher voltages not permissible even briefly)
Cable length
● Cable length, shielded, max. 200 m; Max. 20 m for TWA 100 µs
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
Settling time
● for resistive load 0.05 ms
● for capacitive load 0.05 ms; at a load of up to 500 ohms/100 nF and a max. cable length of 20 m
● for inductive load 0.05 ms
Errors/accuracies
Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.03 %; with resistive load
Temperature error (relative to output range), (+/-) 0.01 %/K
Crosstalk between the outputs, min. -60 dB
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) 0.03 %
Operational limit in overall temperature range
● Current, relative to output area, (+/-) 0.2 %; Specified value applies to loads from 200 to 350 Ohm, deviating operational limits for loads up to 200 Ohm and from 350 to 500 Ohm with up to 0.4%
Basic error limit (operational limit at 25 °C)
● Current, relative to output area, (+/-) 0.1 %; Specified value applies for loads from 200 to 350 ohms, deviating basic error limits for loads up to 200 ohms and from 350 to 500 ohms with up to 0.3%
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Substitute values connectable Yes
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Wire break Yes
● Group error Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 7 byte
Output type/range deactivated / +/-20 mA / 4 to 20 mA
Diagnosis: wire break Disable / enable
Group diagnostics Disable / enable
Behavior on CPU/Master STOP Output current and de-energized/substitute a value/keep last value
Galvanic isolation
Galvanic isolation analog outputs
● Galvanic isolation analog outputs Yes
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Permissible potential difference
between MANA and M internally (UISO) 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 45 g