6ES7134-4GB60-0AB0 ET200S, EL-MOD., 2AI HS I-4DMU, 0-20MA

Product Code: 6ES7134-4GB60-0AB0

Availability: In Stock

Price: $154.13
  
 
Artikelnummer 6ES7134-4GB60-0AB0
SIMATIC DP, ELECTRONIC MODULE 2AI HIGH SPEED I-4WIRE FOR ET 200S, 15 MM WIDE, 4 .. 20MA; 12 BIT, FOR 4-WIRE TRANSDUCER, CYCLE TIME OF THE MODULE: 1MS WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
Input current
from load voltage L+ (without load), max. 35 mA
from backplane bus 3.3 V DC, max. 10 mA
Power losses
Power loss, typ. 0.8 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input current for current input (destruction limit), max. 35 mA
Cycle time (all channels) max. 1 ms
Input ranges
● Current Yes
Input ranges (rated values), currents
● 4 to 20 mA Yes
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle Actual value encryption
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit
● Conversion time (per channel) 0.1 ms
Smoothing of measured values
● Parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.1 %
Operational limit in overall temperature range
● Current, relative to input area, (+/-) 1 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.7 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Interrupts/diagnostics/status information
Diagnostic messages
● Wire break Yes
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 4 byte
Diagnosis: wire break Disable / enable
Measurement type/range deactivated / 4 to 20 mA
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ No
Permissible potential difference
between MANA and M internally (UISO) 75 VDC / 60 VAC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 17.09.2014