6ES7134-4FB51-0AB0 ET200S, EL-MOD., 2AI HS U, +/-10V, 14BIT

Product Code: 6ES7134-4FB51-0AB0

Availability: In Stock

Price: $143.85
  
 
Artikelnummer 6ES7134-4FB51-0AB0
SIMATIC DP, ELECTRONIC MODULE ET 200S: 2 AI HIGH SPEED U, +/-10V; 14 BIT, 15 MM WIDE, CYCLE TIME OF THE MODULE: 1MS, WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 35 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.8 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 50 V; 50 V continuous; 100 V for max. 1 ms (mark to space ratio 1:20)
Cycle time (all channels) max. 1 ms; Per module
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 1 to 5 V Yes
● Input resistance (1 to 5 V) 100 kΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
● Input resistance (-2.5 V to +2.5 V) 100 kΩ
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
Cable length
● Cable length, shielded, max. 200 m
Analog value generation
Measurement principle Actual value encryption
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 14 bit; +/-10 V: 13 bits + sign, +/-5 V: 13 bits + sign, +/-2.5 V: 13 bits + sign; 1 to 5 V: 13 bits
● Conversion time (per channel) 0.1 ms
Smoothing of measured values
● parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1 x cycle time
● Step: Low Yes; 64 x cycle time
● Step: Medium Yes; 128 x cycle time
● Step: High Yes; 512x cycle time
Encoder
Connection of signal encoders
● for voltage measurement Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.01 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input area, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input area, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode interference (USS < 2.5 V) , min. 70 dB; Ucm < 100 Vpp
Isochronous mode
Isochronous mode (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Alarms
● Hardware interrupt Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
● Wire-break No
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 12 byte
Measurement type/range deactivated / +/-10 V / +/-5 V, +/-2.5 V, to 5 V
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ Yes
Permissible potential difference
between inputs and MANA (UCM) 100 Vpp AC
between MANA and M internally (UISO) 75 VDC / 60 VAC
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: