6ES7132-4BB01-0AB0 ET200S, EL-MOD., 2DO HF,DC24V, 0.5A, 5PC

Product Code: 6ES7132-4BB01-0AB0

Availability: In Stock

Price: $88.37
  
 
Artikelnummer 6ES7132-4BB01-0AB0
SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO HIGH FEATURE 24V DC, 15 MM WIDTH DIAGNOSIS F. SHORT-CIRCUIT AND OPEN-CIRCUIT, FIRST-UP SIGNAL WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT
Supply voltage
Reverse voltage protection Yes; when using the same load voltage as on the power module
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes; polarity reversal can lead to the digital outputs being connected through
Input current
from load voltage L+ (without load), max. 5 mA; Per channel
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.4 W
Address area
Address space per module
● with packing 2 bit
● without packing 1 byte
Digital outputs
Number of digital outputs 2
Short-circuit protection Yes
● Response threshold, typ. 1,5 A
Limitation of inductive shutdown voltage to -55 to -60 V, typ. L+( )
Controlling a digital input Yes
Switching capacity of the outputs
● Lamp load, max. 2.5 W
Load resistance range
● lower limit 48 Ω
● upper limit 3 400 Ω
Output voltage
● for signal "1", min. L+ (-1 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range for 0 to 60 °C, min. 7 mA
● for signal "1" permissible range for 0 to 60 °C, max. 600 mA
● for signal "0" residual current, max. 0.3 mA
Output delay with resistive load
● "0" to "1", max. 100 µs
● "1" to "0", max. 400 µs
Parallel switching of 2 outputs
● for uprating No
● for redundant control of a load Yes; per module
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 2 Hz
● on lamp load, max. 10 Hz
Total current of the outputs (per group)
all mounting positions
— up to 60 °C, max. 1 A
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Isochronous mode
Isochronous mode (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Substitute values connectable Yes; 0/1
Diagnostic messages
● Diagnostic functions Yes; Can be read out
● Wire-break Yes; channel by channel
● Short-circuit Yes; channel by channel
Diagnostics indication LED
● Group error SF (red) Yes
● Status indicator digital output (green) Yes
Parameter
Remark 3 byte
Diagnostics wire break Disable / enable
Diagnostics short-circuit Disable / enable
Behavior on CPU/master STOP, channel-wise Substitute a value/keep last value
Galvanic isolation
Galvanic isolation digital outputs
● between the channels No
● between the channels and the backplane bus Yes
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: