SIMATIC S7-200, DIGITAL OUTPUT EM 222, FOR S7-22X CPU ONLY, 4DO, 4-24V DC; 5 A/POINT SOURCE |
|
Supply voltage |
Load voltage L+ |
Rated value (DC) |
24 V |
permissible range, lower limit (DC) |
20.4 V |
permissible range, upper limit (DC) |
28.8 V |
Input current |
from backplane bus 5 V DC, max. |
40 mA |
Power loss |
Power loss, typ. |
3 W |
Digital outputs |
Number of digital outputs |
4 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
L+ (-48 V) |
Output voltage |
for signal "1", min. |
20 V DC |
Output current |
for signal "1" permissible range for 0 to 40 °C, max. |
5 A |
for signal "1" permissible range for 0 to 55 °C, max. |
5 A |
for signal "0" residual current, max. |
30 µA |
Total current of the outputs (per group) |
all mounting positions |
up to 40 °C, max. |
20 A |
maximum current per conductor/group |
5 A |
horizontal installation |
up to 55 °C, max. |
20 A |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. |
5 A |
on lamp load, max. |
50 W |
with resistive load, max. |
5 A |
Cable length |
Cable length, shielded, max. |
500 m |
Cable length unshielded, max. |
150 m |
Galvanic isolation |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs |
Yes |
between the channels, in groups of |
1 |
Connection method |
Plug-in I/O terminals |
Yes |
Dimensions |
Width |
45 mm |
Height |
80 mm |
Depth |
62 mm |
Weights |
Weight, approx. |
120 g |
Status |
Jul 7, 2014 |