SIMATIC S7-200, DIGITAL OUTPUT EM 222, OPTICALLY ISOLATED 8DQ, 120/230V AC, 0.5A |
|
Supply voltage |
Load voltage L1 |
Rated value (AC) |
230 V |
permissible range, lower limit (AC) |
65 V |
permissible range, upper limit (AC) |
264 V |
permissible frequency range, lower limit |
47 Hz |
permissible frequency range, upper limit |
63 Hz |
Input current |
from backplane bus 5 V DC, max. |
110 mA |
Power losses |
Power loss, typ. |
4 W |
Digital outputs |
Number of digital outputs |
8 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
to be provided externally (see manual package "Setting up an S7-200") |
Output voltage |
for signal "1", min. |
L1 (-0.9 V) |
Output current |
for signal "1" permissible range for 0 to 40 °C, max. |
500 mA; AC |
for signal "1" permissible range for 0 to 55 °C, max. |
500 mA; AC |
for signal "1" minimum load current |
50 mA |
for signal "0" residual current, max. |
1.8 mA |
Aggregate current of outputs (per group) |
all mounting positions |
up to 40 °C, max. |
0.5 A |
maximum current per conductor/group |
0.5 A |
horizontal installation |
up to 55 °C, max. |
0.5 A |
Relay outputs |
Switching capacity of contacts |
with inductive load, max. |
0.5 A |
on lamp load, max. |
60 W |
with resistive load, max. |
0.5 A |
Cable length |
Cable length, shielded, max. |
500 m |
Cable length unshielded, max. |
150 m |
Galvanic isolation |
Galvanic isolation digital outputs |
Galvanic isolation digital outputs |
Yes |
between the channels, in groups of |
1; 8 groups |
Connection method |
Plug-in I/O terminals |
Yes |
Dimensions |
Width |
71.2 mm |
Height |
80 mm |
Depth |
62 mm |
Weights |
Weight, approx. |
170 g |
Status |
May 9, 2014 |