Supply voltage |
Load voltage L+ |
● Rated value (DC) |
60 V |
● permissible range, lower limit (DC) |
1 V |
● permissible range, upper limit (DC) |
60 V |
Load voltage L1 |
● Rated value (AC) |
230 V |
● permissible range, lower limit (AC) |
2 V |
● permissible range, upper limit (AC) |
264 V |
Input current |
from backplane bus 5 V DC, max. |
1 A |
Power losses |
Power loss, max. |
25 W |
Digital outputs |
Number of digital outputs |
16; Relays |
Switching capacity of the outputs |
● Lamp load, max. |
60 W |
Output current |
● for signal "1" rated value |
5 A |
Switching frequency |
● with resistive load, max. |
10 Hz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 60 °C, max. |
5 mA; 10 A with fan subassembly |
Relay outputs |
● Number of operating cycles, max. |
100 000; 100,000 (AC 15 / DC 13); 3,000,000 mechanical |
Switching capacity of contacts |
— with inductive load, max. |
5 A; 5 A (30 V DC); 5 A (230 V AC) |
— with resistive load, max. |
5 A; 5 A (30 V DC); 5 A (230 V AC); 1.2 A (60 V DC); 0.2 A (125 V DC) |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
2 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
1500 V AC |
Dimensions |
Width |
25 mm |
Height |
290 mm |
Depth |
210 mm |
Weights |
Weight, approx. |
700 g |
last modified: |
26.09.2014 |