6ES7412-1XF03-0AB0 SIMATIC S7-400, CPU 412-1

Product Code: 6ES7412-1XF03-0AB0

Availability: In Stock

Price: $1,036.41
  
 
Artikelnummer 6ES7412-1XF03-0AB0
SIMATIC S7-400, CPU 412-1 96 KB WORKING MEMORY (48 KB CODE, 48 KB DATA) INTERFACE MPI/DP 12 MBIT/S
CiR - Configuration in RUN
CiR synchronization time, basic load 100 ms
CiR synchronization time, time per I/O slave 200 µs
Supply voltage
24 V DC Yes
Input current
from backplane bus 5 V DC, typ. 1.5 A
from backplane bus 5 V DC, max. 1.6 A
from backplane bus 24 V DC, max. 150 mA; Total current consumption of the components connected to the MPI/DP interfaces, but no more than 150 mA per interface
Power losses
Power loss, typ. 7.5 W
Memory
Data and program memory
● Data memory, max. 48 kbyte
● Program memory, max. 48 kbyte
Work memory
● Integrated 96 kbyte
● expandable No
Load memory
● expandable FEPROM Yes; with Memory Card (FLASH)
● expandable FEPROM, max. 64 Mbyte
● integrated RAM, max. 256 kbyte
● expandable RAM Yes; with Memory Card (RAM)
● expandable RAM, max. 64 Mbyte
Backup
● present Yes
● with battery Yes; all data
● without battery No
Battery
Backup battery
● Backup current, typ. 40 µA
● Backup current, max. 300 µA
● Feeding of external backup voltage to CPU 5 to 15 VDC
CPU processing times
for bit operations, typ. 0.2 µs
for word operations, typ. 0.2 µs
for fixed point arithmetic, typ. 0.2 µs
for floating point arithmetic, typ. 0.6 µs
CPU-blocks
DB
● Number, max. 512; DB 0 reserved
● Size, max. 48 kbyte
FB
● Number, max. 256
● Size, max. 48 kbyte
FC
● Number, max. 256
● Size, max. 48 kbyte
OB
● Number, max. see instruction list
● Size, max. 48 kbyte
● Number of time alarm OBs 2
● Number of delay alarm OBs 2
● Number of time interrupt OBs 2
● Number of process alarm OBs 2
Nesting depth
● per priority class 24
● additional within an error OB 2
Counters, timers and their retentivity
S7 counter
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset Z 0 to Z 7
Counting range
— lower limit 1
— upper limit 999
IEC counter
● present Yes
● Type SFB
S7 times
● Number 256
Retentivity
— can be set Yes
— lower limit 0
— upper limit 255
— preset No retentivity
Time range
— lower limit 10 ms
— upper limit 9 990 s
IEC timer
● present Yes
● Type SFB
Data areas and their retentivity
retentive data area, total Total working and load memory (with backup battery)
Flag
● Number, max. 4 kbyte
● Retentivity available Yes; From MB 0 to MB 4095
● Retentivity preset MB 0 to MB 15
● Number of clock memories 8; 1 memory byte
Data blocks
● Number, max. 512; DB 0 reserved
● Size, max. 64 kbyte
Address area
I/O address area
● Inputs 4 kbyte
● Outputs 4 kbyte
of which, distributed
— MPI/DP interface, inputs 2 kbyte
— MPI/DP interface, outputs 2 kbyte
Process image
● Inputs, adjustable 4 kbyte; adjustable at the expense of the code area of the RAM
● Outputs, adjustable 4 kbyte; adjustable at the expense of the code area of the RAM
● Inputs, default 128 byte; adjustable at the expense of the code area of the RAM
● Outputs, default 128 byte; adjustable at the expense of the code area of the RAM
● consistent data, max. 244 byte
● Access to consistent data in process image Yes
Subprocess images
● Number of subprocess images, max. 8
Digital channels
● Inputs 32 768
● Outputs 32 768
● Inputs, of which central 32 768
● Outputs, of which central 32 768
Analog channels
● Inputs 2 048
● Outputs 2 048
● Inputs, of which central 2 048
● Outputs, of which central 2 048
Hardware configuration
Expansion devices, max. 21; of which 6 ER with K-bus
connectable OPs 16 without message processing, 8 with message processing
Multicomputing Yes; 4 CPUs max. (with UR1 or UR2)
Interface modules
● Number of connectable IMs (total), max. 6
● Number of connectable IM 460s, max. 6
● Number of connectable IM 463s, max. 4; IM 463-2
Number of DP masters
● Integrated 1
● via IM 467 4
● Via CP 10
● Mixed mode IM + CP permitted No; IM 467 cannot be used jointly with CP 443-5 Ext.
● via interface module 0
● Number of pluggable S5 modules (via adapter capsule in central device), max. 6
Number of operable FMs and CPs (recommended)
● FM 16; Limited by number of slots and number of connections
● CP, point-to-point 16; limited by number of slots
● CP, LAN 16; limited by number of slots and number of connections; for S5-compatible communication max. 4
● PROFIBUS and Ethernet CPs 14; incl. CP 443-5 Ext. and IM 467
Slots
● Required slots 1
Time of day
Clock
● Hardware clock (real-time clock) Yes
● battery-backed and synchronizable Yes
● Resolution 1 ms
Operating hours counter
● Number 8
Clock synchronization
● supported Yes
● to MPI, master Yes
● to MPI, slave Yes
● to DP, master Yes
● to DP, slave Yes
● in AS, master Yes
● in AS, slave Yes
1st interface
Physics RS 485 / PROFIBUS
Isolated Yes
Number of connection resources MPI: 16, DP: 16
Functionality
● MPI Yes
● DP master Yes
● DP slave Yes
MPI
● Number of connections 16
● Transmission rate, max. 12 Mbit/s
Services
— PG/OP communication Yes
— Routing Yes
— Global data communication Yes
— S7 basic communication Yes
— S7 communication Yes
DP master
● Number of connections, max. 16
● Transmission rate, max. 12 Mbit/s
● Number of DP slaves, max. 32
Services
— PG/OP communication Yes
— Global data communication No
— S7 basic communication No
— S7 communication Yes
— Equidistance mode support Yes
— SYNC/FREEZE Yes
— Activation/deactivation of DP slaves Yes
— Direct data exchange (slave-to-slave communication) Yes
Address area
— Inputs, max. 2 kbyte
— Outputs, max. 2 kbyte
User data per DP slave
— Inputs, max. 244 byte
— Outputs, max. 244 byte
— Slots, max. 244
— per slot, max. 128 byte
DP slave
● Transmission rate, max. 12 Mbit/s
● Address area, max. 32
● User data per address area, max. 32 byte
● User data per address area, of which consistent, max. 32 byte
Services
— PG/OP communication Yes; with interface active
— Routing Yes; with interface active
Transfer memory
— Inputs 244 byte
— Outputs 244 byte
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
User data per isochronous slave, max. 128 byte
equidistance Yes
shortest clock pulse 5 ms; 2.5 ms without using the SFCs 126 / 127
Communication functions
PG/OP communication Yes
Global data communication
● supported Yes
● Number of GD packets, transmitter, max. 8
● Number of GD packets, receiver, max. 16
● Size of GD packets, max. 64 byte
S7 basic communication
● supported Yes
● User data per job, max. 76 byte
S7 communication
● supported Yes
● as server Yes
● As client Yes
● User data per job, max. 64 kbyte
S5-compatible communication
● supported Yes; via CP and FC AG_SEND and FC AG_RECV
● User data per job, max. 8 kbyte
Standard communication (FMS)
● supported Yes; Via CP and loadable FB
Number of connections
● overall 16; of which one is reserved for PG and OP
● usable for PG communication
— reserved for PG communication 1
— Adjustable for PG communication, max. 0
● usable for OP communication
— reserved for OP communication 1
— adjustable for OP communication, max. 0
● usable for S7 basic communication
— Reserved for S7 basic communication 0
— adjustable for S7 basic communication, max. 0
● usable for S7 communication
— reserved for S7 communication 0
— Adjustable for S7 communication, max. 0
● usable for routing 0
— Reserved for routing 0
— adjustable for routing, max. 0
S7 message functions
Number of login stations for message functions, max. 8
Symbol-related messages Yes
Block related messages Yes
Alarm 8-blocks Yes
Process control messages Yes
Test commissioning functions
Status block Yes
Single step Yes
Number of breakpoints 4
Status/control
● Status/control variable Yes
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
● Number of entries, max. 200
— can be set Yes
Configuration
Configuration software
● STEP 7 Yes
programming
● Nesting levels 8
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC Yes
— GRAPH Yes
— HiGraph® Yes
Know-how protection
● User program protection/password protection Yes
Dimensions
Width 25 mm
Height 290 mm
Depth 219 mm
Weights
Weight, approx. 720 g