6ES7235-0KD22-0XA0 SIMATIC S7-200, ANALOG I/O

Product Code: 6ES7235-0KD22-0XA0

Availability: In Stock

Price: $161.66
  
 
Artikelnummer 6ES7235-0KD22-0XA0
SIMATIC S7-200, ANALOG I/O EM 235, FOR S7-22X CPU ONLY, 4 AI, DC +/-10V; 1AQ, DC +/-10V 12 BIT CONVERTER
Input current
from backplane bus 5 V DC, max. 30 mA
from sensor current supply or external current supply (24 V DC), max. 60 mA
Power losses
Power loss, typ. 2 W
Analog inputs
Number of analog inputs 4; Difference
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 32 mA
Input ranges
● Voltage Yes
● Current Yes
Input ranges (rated values), voltages
● 0 to +50 mV Yes
● 0 to +100 mV Yes
● 0 to +500 mV Yes
● 0 to +1 V Yes
● 0 to +5 V Yes
● 0 to +10 V Yes
● -1 V to +1 V Yes
● -10 V to +10 V Yes
● -100 mV to +100 mV Yes
● -2.5 V to +2.5 V Yes
● -25 mV to +25 mV Yes
● -250 mV to +250 mV Yes
● -5 V to +5 V Yes
● -50 mV to +50 mV Yes
● -500 mV to +500 mV Yes
Input ranges (rated values), currents
● 0 to 20 mA Yes
Thermocouple (TC)
Temperature compensation
— Parameterizable No
Analog outputs
Number of analog outputs 1
Output ranges, voltage
● -10 to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 5 kΩ
● with current outputs, max. 0.5 kΩ
Analog value creation
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 12 bit; 11 bits for current output
● Basic conversion time, ms < 0.25 ms
● Interference voltage suppression for interference frequency f1 in Hz 40 dB, DC to 60 Hz
Settling time
● for voltage output 100 µs
● for current output 2 ms
Displayable conversion value range
● bipolar signals -32 000 to +32 000
● unipolar signals 0 to 32000
Errors/accuracies
Operational limit in overall temperature range
● Voltage, relative to output area, (+/-) 2 %
● Current, relative to output area, (+/-) 2 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output area, (+/-) 0.5 %
● Current, relative to output area, (+/-) 0.5 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Diagnostics indication LED
● External fault EXTF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
● Galvanic isolation analog inputs No
Galvanic isolation analog outputs
● Galvanic isolation analog outputs No
Connection method
Plug-in I/O terminals No
Dimensions
Width 71.2 mm
Height 80 mm
Depth 62 mm
Weights
Weight, approx. 186 g
last modified: 22.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: