6ES7216-2BD23-0XB0 CPU 226, AC PS, 24DI DC/16DO RELAY

Product Code: 6ES7216-2BD23-0XB0

Availability: In Stock

Price: $398.67
  
 
Artikelnummer 6ES7216-2BD23-0XB0
Supply voltage
120 V AC Yes
230 V AC Yes
Line frequency
● permissible frequency range, upper limit 63 Hz
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 5 V
● permissible range, upper limit (DC) 30 V
Load voltage L1
● Rated value (AC) 100 V
● permissible range, lower limit (AC) 5 V
● permissible range, upper limit (AC) 250 V
● permissible frequency range, lower limit 47 Hz
● permissible frequency range, upper limit 63 Hz
Input current
Inrush current, max. 20 A
from supply voltage L1, max. 320 mA
Encoder supply
24 V encoder supply
● 24 V Yes
● short-circuit protection Yes
● Output current, max. 400 mA
Memory
Number of memory modules (optional) 1
Data and program memory
● Data memory, max. 10 kbyte
● Program memory, max. 24 kbyte
Backup
● present Yes
Battery
Backup battery
● Backup time, max. 100 h
CPU processing times
for bit operations, max. 0.22 µs
Counters, timers and their retentivity
S7 counter
● Number 256
of which retentive with battery
— can be set Yes
— lower limit 1
— upper limit 256
Counting range
— lower limit 0
— upper limit 32 767
S7 times
● Number 256
of which retentive with battery
— can be set Yes
— upper limit 64
Time range
— lower limit 1 ms
— upper limit 54 min
Data areas and their retentivity
Flag
● Number, max. 32 byte
● Retentivity available Yes
Hardware configuration
Expansion devices, max. 7
Expansion modules
● Analog inputs/outputs, max. 35
● Digital inputs/outputs, max. 148
● AS-Interface inputs/outputs max. 62
Digital inputs
Number of digital inputs 24
m/p-reading Yes
Input voltage
● Rated value, DC 24 V
Input current
● for signal "1", typ. 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— Parameterizable Yes
— at "0" to "1", min. 0.2 ms
— at "0" to "1", max. 12.8 ms
for interrupt inputs
— Parameterizable Yes
for counter/technological functions
— Parameterizable Yes
Cable length
● Cable length, shielded, max. 500 m
● Cable length unshielded, max. 300 m
Digital outputs
Number of digital outputs 16
short-circuit protection No
Switching capacity of the outputs
● with resistive load, max. 2 A
● on lamp load, max. 200 W
Output current
● for signal "1" rated value 2 A
● for signal "0" residual current, max. 0 mA
Output delay with resistive load
● "0" to "1", max. 10 ms
● "1" to "0", max. 10 ms
Parallel switching of 2 outputs
● for increased power No
Switching frequency
● of the pulse outputs, with resistive load, max. 1 kHz
Aggregate current of outputs (per group)
all mounting positions
— up to 40 °C, max. 10 A
horizontal installation
— up to 55 °C, max. 10 A
Relay outputs
● Max. number of relay outputs, integrated 16
● Number of operating cycles, max. 10 000 000
Cable length
● Cable length, shielded, max. 500 m
● Cable length unshielded, max. 150 m
Analog inputs
Number of analog potentiometers 2
Encoder
Connectable encoders
● 2-wire sensor Yes
— Permissible quiescent current (2-wire sensor), max. 1 mA
1st interface
Functionality
● MPI Yes
● PPI Yes
● Serial data exchange Yes
MPI
● Transmission rate, min. 19.2 kbit/s
● Transmission rate, max. 187.5 kbit/s
2nd interface
Functionality
● MPI Yes
● PPI Yes
● Serial data exchange Yes
MPI
● Transmission rate, min. 19.2 kbit/s
● Transmission rate, max. 187.5 kbit/s
Integrated Functions
Number of counters 6
Counter frequency (counter) max. 30 kHz
Number of alarm inputs 4
Galvanic isolation
Galvanic isolation digital inputs
● between the channels Yes
Galvanic isolation digital outputs
● between the channels Yes
Degree and class of protection
Degree of protection to EN 60529
● IP20 Yes
Ambient conditions
Operating temperature
● horizontal installation, min. 0 °C
● horizontal installation, max. 55 °C
● vertical installation, min. 0 °C
● vertical installation, max. 45 °C
Air pressure
● permissible range, min. 860 hPa
● permissible range, max. 1 080 hPa
Relative humidity
● Operation, min. 5 %
● Operation, max. 95 %
Configuration
programming
● Number of subroutines, max. 64
Programming language
— LAD Yes
— FBD Yes
— STL Yes
Know-how protection
● User program protection/password protection Yes
Connection method
Plug-in I/O terminals Yes
Dimensions
Width 196 mm
Height 80 mm
Depth 62 mm
Weights
Weight, approx. 660 g
last modified: 16.09.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: