Supply voltage |
120 V AC |
Yes |
230 V AC |
Yes |
Line frequency |
● permissible frequency range, upper limit |
63 Hz |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
5 V |
● permissible range, upper limit (DC) |
30 V |
Load voltage L1 |
● Rated value (AC) |
100 V |
● permissible range, lower limit (AC) |
5 V |
● permissible range, upper limit (AC) |
250 V |
● permissible frequency range, lower limit |
47 Hz |
● permissible frequency range, upper limit |
63 Hz |
Input current |
Inrush current, max. |
20 A |
from supply voltage L1, max. |
320 mA |
Encoder supply |
24 V encoder supply |
● 24 V |
Yes |
● short-circuit protection |
Yes |
● Output current, max. |
400 mA |
Memory |
Number of memory modules (optional) |
1 |
Data and program memory |
● Data memory, max. |
10 kbyte |
● Program memory, max. |
24 kbyte |
Backup |
● present |
Yes |
Battery |
Backup battery |
● Backup time, max. |
100 h |
CPU processing times |
for bit operations, max. |
0.22 µs |
Counters, timers and their retentivity |
S7 counter |
● Number |
256 |
of which retentive with battery |
— can be set |
Yes |
— lower limit |
1 |
— upper limit |
256 |
Counting range |
— lower limit |
0 |
— upper limit |
32 767 |
S7 times |
● Number |
256 |
of which retentive with battery |
— can be set |
Yes |
— upper limit |
64 |
Time range |
— lower limit |
1 ms |
— upper limit |
54 min |
Data areas and their retentivity |
Flag |
● Number, max. |
32 byte |
● Retentivity available |
Yes |
Hardware configuration |
Expansion devices, max. |
7 |
Expansion modules |
● Analog inputs/outputs, max. |
35 |
● Digital inputs/outputs, max. |
148 |
● AS-Interface inputs/outputs max. |
62 |
Digital inputs |
Number of digital inputs |
24 |
m/p-reading |
Yes |
Input voltage |
● Rated value, DC |
24 V |
Input current |
● for signal "1", typ. |
2.5 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— Parameterizable |
Yes |
— at "0" to "1", min. |
0.2 ms |
— at "0" to "1", max. |
12.8 ms |
for interrupt inputs |
— Parameterizable |
Yes |
for counter/technological functions |
— Parameterizable |
Yes |
Cable length |
● Cable length, shielded, max. |
500 m |
● Cable length unshielded, max. |
300 m |
Digital outputs |
Number of digital outputs |
16 |
short-circuit protection |
No |
Switching capacity of the outputs |
● with resistive load, max. |
2 A |
● on lamp load, max. |
200 W |
Output current |
● for signal "1" rated value |
2 A |
● for signal "0" residual current, max. |
0 mA |
Output delay with resistive load |
● "0" to "1", max. |
10 ms |
● "1" to "0", max. |
10 ms |
Parallel switching of 2 outputs |
● for increased power |
No |
Switching frequency |
● of the pulse outputs, with resistive load, max. |
1 kHz |
Aggregate current of outputs (per group) |
all mounting positions |
— up to 40 °C, max. |
10 A |
horizontal installation |
— up to 55 °C, max. |
10 A |
Relay outputs |
● Max. number of relay outputs, integrated |
16 |
● Number of operating cycles, max. |
10 000 000 |
Cable length |
● Cable length, shielded, max. |
500 m |
● Cable length unshielded, max. |
150 m |
Analog inputs |
Number of analog potentiometers |
2 |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1 mA |
1st interface |
Functionality |
● MPI |
Yes |
● PPI |
Yes |
● Serial data exchange |
Yes |
MPI |
● Transmission rate, min. |
19.2 kbit/s |
● Transmission rate, max. |
187.5 kbit/s |
2nd interface |
Functionality |
● MPI |
Yes |
● PPI |
Yes |
● Serial data exchange |
Yes |
MPI |
● Transmission rate, min. |
19.2 kbit/s |
● Transmission rate, max. |
187.5 kbit/s |
Integrated Functions |
Number of counters |
6 |
Counter frequency (counter) max. |
30 kHz |
Number of alarm inputs |
4 |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels |
Yes |
Galvanic isolation digital outputs |
● between the channels |
Yes |
Degree and class of protection |
Degree of protection to EN 60529 |
|
● IP20 |
Yes |
Ambient conditions |
Operating temperature |
● horizontal installation, min. |
0 °C |
● horizontal installation, max. |
55 °C |
● vertical installation, min. |
0 °C |
● vertical installation, max. |
45 °C |
Air pressure |
● permissible range, min. |
860 hPa |
● permissible range, max. |
1 080 hPa |
Relative humidity |
● Operation, min. |
5 % |
● Operation, max. |
95 % |
Configuration |
programming |
● Number of subroutines, max. |
64 |
Programming language |
— LAD |
Yes |
— FBD |
Yes |
— STL |
Yes |
Know-how protection |
● User program protection/password protection |
Yes |
Connection method |
Plug-in I/O terminals |
Yes |
Dimensions |
Width |
196 mm |
Height |
80 mm |
Depth |
62 mm |
Weights |
Weight, approx. |
660 g |
last modified: |