6ES7144-6KD00-0AB0 ET200ECO PN, 8AI; 4 U/I; 4 RTD/TC 8XM12

Product Code: 6ES7144-6KD00-0AB0

Availability: In Stock

Price: $301.40
  
 
Artikelnummer 6ES7144-6KD00-0AB0
SIMATIC DP, ET 200ECO PN, 8 AI (4 U/I + 4 RTD/TC); 8XM12, DEGREE OF PROTECTION IP67
General information
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0306H
Supply voltage
24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, typ. 110 mA
Encoder supply
Number of outputs 4
24 V encoder supply
● Short-circuit protection Yes; Electronic at 1.4 A
● Output current, max. 1 A
Power loss
Power loss, typ. 2.8 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for voltage/current measurement 4
Number of analog inputs for resistance/resistance thermometer measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V permanent, 35 V for max. 500 ms
Input ranges (rated values), voltages
● 0 to +10 V Yes
● 1 to 5 V Yes
● -10 V to +10 V Yes
● -80 mV to +80 mV Yes
Input ranges (rated values), currents
● 0 to 20 mA Yes
● -20 to +20 mA Yes
● 4 to 20 mA Yes
Input ranges (rated values), thermocouples
● Type E Yes
● Type J Yes
● Type K Yes
● Type N Yes
Input ranges (rated values), resistance thermometers
● Ni 100 Yes
● Ni 1000 Yes
● Ni 120 Yes
● Ni 200 Yes
● Ni 500 Yes
● Pt 100 Yes
● Pt 1000 Yes
● Pt 200 Yes
● Pt 500 Yes
Input ranges (rated values), resistors
● 0 to 150 Ohm Yes
● 0 to 300 Ohm Yes
● 0 to 600 Ohm Yes
● 0 to 3000 Ohm Yes
Thermocouple (TC)
Temperature compensation
— parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation with compensations socket Yes
Cable length
● Cable length, shielded, max. 30 m
Analog value generation
Analog value display SIMATIC S7 format
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution (incl. overrange) 15 bits + sign
● Integration time, parameterizable Yes
● Integration time, ms 2/16.67/20/100 ms
● Interference voltage suppression for interference frequency f1 in Hz 500 / 60 / 50 / 10 Hz
● Conversion time (per channel) 4 / 19 / 22 / 102 ms
Smoothing of measured values
● parameterizable Yes
● Step: None Yes; 1 x cycle time
● Step: Low Yes; 4 x cycle time
● Step: Medium Yes; 16 x cycle time
● Step: High Yes; 64 x cycle time
Encoder
Number of connectable encoders, max. 8
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) U: 0.0035%/°C; I:0.006%/°C; RTD: 0.0005%/°C; TC: 0.0035%/°C
Crosstalk between the inputs, min. 85 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.008 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 46 dB
● Common mode interference, min. 70 dB
Interfaces
Transmission procedure 100BASE-TX
Transmission rate, max. 100 Mbit/s
PROFINET IO
● Number of PROFINET interfaces 1
● Autocrossing Yes
● automatic detection of transmission rate Yes
● integrated switch Yes
PROFINET IO Device
— IRT with the option "high flexibility", supported Yes
— Prioritized startup Yes
Protocols
PROFINET IO Yes
PROFINET CBA No
PROFIsafe No
Protocols (Ethernet)
● SNMP Yes
● DCP Yes
● LLDP Yes
● ping Yes
● ARP Yes
Interrupts/diagnostics/status information
Status indicator Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Diagnostic functions Yes
● Diagnostic information readable Yes
● Monitoring the supply voltage Yes; Green "ON" LED
● Short-circuit encoder supply Yes; per module
● Group error Yes; Red/yellow "SF/MT" LED
● Overflow/underflow Yes
Galvanic isolation
between the load voltages Yes
between load voltage and all other switching components No
between Ethernet and electronics Yes
Galvanic isolation analog inputs
● between the channels No
Permissible potential difference
between inputs and MANA (UCM) 10 Vpp AC
Isolation
tested with
● 24 V DC circuits 500 V
● Interface 1 500 V; According to IEEE 802.3
Degree and class of protection
IP65 Yes
IP66 Yes
IP67 Yes
Connection method
M12 Yes
Dimensions
Width 60 mm
Height 175 mm
Depth 49 mm
Weights
Weight (without packaging) 930 g