6ES7134-7SD50-0AB0 ET200ISP, EL-MOD., 4 AI RTD, PT100/NI100

Product Code: 6ES7134-7SD50-0AB0

Availability: In Stock

Price: $307.57
  
 
Artikelnummer 6ES7134-7SD50-0AB0
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI, RTD, FOR CONNECTION OF RESISTANCE THERMOMETER PT100/NI100
Input current
from supply voltage L+, max. 22 mA
Power loss
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 4
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustable Yes
Input ranges
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), resistance thermometers
● Ni 100 Yes
● Input resistance (Ni 100) 2 000 kΩ
● Pt 100 Yes
● Input resistance (Pt 100) 2 000 kΩ
Input ranges (rated values), resistors
● Input resistance (0 to 600 Ohm) 0.6 kΩ
Characteristic linearization
● parameterizable Yes
— for resistance thermometer Yes
Cable length
● Cable length, shielded, max. 500 m
Analog value generation
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Basic conversion time, including integration time, ms 80 ms at 50 Hz; 66 ms at 60 Hz
— additional conversion time for wire-break monitoring 5
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes; in 4 stages
● Step: None Yes; 1 x cycle time
● Step: Low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Encoder
Connection of signal encoders
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.015 %
Temperature error (relative to input range), (+/-) 0.02 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.01 %
Operational error limit in overall temperature range
● Resistance thermometer, relative to input area, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C)
● Resistance thermometer, relative to input area, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode interference, min. 90 dB
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
● Limit value alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
● Wire-break Yes
Diagnostics indication LED
● Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
● between the channels Yes
● between the channels and the backplane bus Yes
Standards, approvals, certificates
CE mark Yes
Use in hazardous areas
● Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
● Type of protection acc. to KEMA 04 ATEX 1247
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weights
Weight, approx. 230 g