6ES7134-4GD00-0AB0 ET200S, EL-MOD., 4AI STANDARD I 2-WIRE

Product Code: 6ES7134-4GD00-0AB0

Availability: In Stock

Price: $95.90
  
 
Artikelnummer 6ES7134-4GD00-0AB0
SIMATIC DP, ELECTRONIC MODULE ET200S, 4AI STANDARD I-2-WIRE, 4 - 20MA; 13BIT, 15MM WIDTH, FOR 2-WIRE TRANSDUCER CYCLE TIME 40 MS/MODULE WITH LED SF (GROUP FAULT)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 125 mA
from backplane bus 3.3 V DC, max. 10 mA
Output voltage
Power supply to the transmitters
● present Yes
● short-circuit proof Yes; approx. 200 mA for module
Power losses
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 8 byte
Analog inputs
Number of analog inputs 4
permissible input current for current input (destruction limit), max. 30 mA; limited electronically
Cycle time (all channels) max. 40 ms; 33 to 40 ms
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● 4 to 20 mA Yes; Into 25 Ohm
Cable length
● Cable length, shielded, max. 200 m
Analog value creation
Measurement principle integrating
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit; 4 to 20 mA: 13 bits
● Integration time, parameterizable Yes
● Integration time, ms 16,67 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 60 / 50 Hz
Smoothing of measured values
● Parameterizable Yes; in 4 stages
● Step: None Yes; 1 x cycle time
● Step: low Yes; 4 x cycle time
● Step: Medium Yes; 16 x cycle time
● Step: High Yes; 32 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.003 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.05 %
Operational limit in overall temperature range
● Current, relative to input area, (+/-) 0.4 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Diagnostic functions Yes; Can be read out
● Wire break Yes; Measuring range 1 to 5 V only
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 7 byte
Diagnosis: wire break 1
Measurement type/range 1
Group diagnostics 1
Overflow/underflow 1
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
● between the channels and the load voltage L+ No
Isolation
Isolation checked with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g