6ES7131-4CD00-0AB0 ET200S, EL-MOD., 4DI, UC 24-48V, 5 PCS

Product Code: 6ES7131-4CD00-0AB0

Availability: In Stock

Price: $119.88
  
 
Digitalausgabemodul 2DO

-
SIMATIC DP, 5 ELECTRON. MODULES ET 200S: 4DI UC 24V...48V, 15 MM WIDTH, WITH LED SF (GROUP FAULT), 5 PIECES PER PACKAGING UNIT
Supply voltage
24 V DC Yes; From power module
permissible range, lower limit (DC) 24 V
permissible range, upper limit (DC) 48 V
24 V AC Yes
permissible range, lower limit (AC) 24 V
permissible range, upper limit (AC) 48 V
Reverse polarity protection Yes; AC or DC automatic
Input current
from backplane bus 3.3 V DC, max. 10 mA
from supply voltage L+, max. Dependent on encoder
Encoder supply
short-circuit protection Yes
Output current
Output current, rated value 500 mA
Output current, permissible range 0 to 500 mA
Power losses
Power loss, typ. 0.7 W
Address area
Address space per module
with packing 4 bit
without packing 1 byte
Digital inputs
Number of digital inputs 4
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Input voltage
Type of input voltage AC/DC
Rated value, UC 24 V; 24 to 48 V UC
for signal "0" -6 to 6 V DC, 0 to 5 V AC
for signal "1" -15 to -57.6 V DC; -15 to 57.6 V DC; 15 to 48 V AC
Frequency range 47 bis 63 Hz
Input current
for signal "1", typ. 10 mA; 4 to 10 mA
Input delay (for rated value of input voltage)
for standard inputs
at "0" to "1", max. 15 ms
at "1" to "0", max. 15 ms
Encoder connection
Fixed current limitation for wire break monitoring, min. 18 kΩ; Rated voltage 24 V (15 V to 35 V); rated voltage 48 V (30 V to 60 V): 39 kohms
Cable length
Cable length, shielded, max. 1000 m
Cable length unshielded, max. 600 m
Encoder
Connectable encoders
2-wire sensor Yes
Permissible quiescent current (2-wire sensor), max. 2 mA; (0.5 to 2 mA), a minimum load current is necessary for wire break diagnostics.
Isochronous mode
Isochronous operation (application synchronized up to terminal) Yes
Interrupts/diagnostics/status information
Diagnostic messages
Diagnostic functions Yes; Parameterizable
Diagnostics indication LED
Group error SF (red) Yes
Status indicator digital input (green) Yes; per channel
Galvanic isolation
Galvanic isolation digital inputs
between the channels No
between the channels and the backplane bus Yes
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 35 g
Status May 14, 2014

Write a review

Note: HTML is not translated!