Product type designation |
CM 1542-1 |
|
COMMUNICATIONS MODULE CM 1542-1 FOR CONNECTING S7-1500 TO PROFINET AS IO-CONTROLLER: TCP/IP, ISO-ON-TCP, UDP, S7-COMMUNICATION, IP-BROADCAST/ MULTICAST, SNMPV1, DHCP, CLOCK SYNCHRONISATION VIA NTP, 2XRJ45 (10/100 MBIT) |
Transmission rate |
Transfer rate |
|
● at the 1st interface |
10 ... 100 Mbit/s |
Interfaces |
Number of interfaces / acc. to Industrial Ethernet |
0 |
Number of electrical connections |
|
● at the 1st interface / acc. to Industrial Ethernet |
2 |
Design of the electrical connection |
|
● at the 1st interface / acc. to Industrial Ethernet |
RJ45 port |
Supply voltage, current consumption, power loss |
Type of voltage / of the supply voltage |
DC |
Supply voltage / 1 / from backplane bus |
15 V |
Relative symmetrical tolerance / for DC |
|
● at 15 V |
3 % |
Consumed current |
|
● from backplane bus / for DC / at 15 V / typical |
0.22 A |
Active power loss |
3.3 W |
Permitted ambient conditions |
Ambient temperature |
|
● for vertical installation / during operation |
0 ... 40 °C |
● for horizontally arranged busbars / during operation |
0 ... 60 °C |
● during storage |
-40 ... +70 °C |
● during transport |
-40 ... +70 °C |
Relative humidity / at 25 °C / without condensation / during operation / maximum |
95 % |
Protection class IP |
IP20 |
Design, dimensions and weight |
Module format |
Compact module S7-1500 single width |
Width |
35 mm |
Height |
142 mm |
Depth |
129 mm |
Net weight |
0.4 kg |
Mounting type |
|
● S7-1500 rail mounting |
Yes |
Product properties, functions, components / general |
Number of units |
|
● per CPU / maximum |
8 |
● Note |
depending on CPU type |
Performance data |
Performance data / open communication |
Number of possible connections / for open communication / by means of T blocks / maximum |
64; depending on the system upper limit |
Amount of data / as user data per ISO on TCP connection / for open communication / by means of T blocks / maximum |
65536 byte |
Number of Multicast stations |
6 |
Performance data / S7 communication |
Number of possible connections / for S7 communication |
|
● maximum |
64 |
● Note |
depending on the system upper limit |
Performance data / multi-protocol mode |
Number of active connections / with multi-protocol mode |
64 |
Performance data / PROFINET communication / as PN IO-Controller |
Product function / PROFINET IO controller |
Yes |
Number of PN IO devices / on PROFINET IO controller / usable / total |
128 |
Number of PN IO IRT devices / on PROFINET IO controller / usable |
64 |
Number of external PN IO lines / with PROFINET / per rack |
10 |
Amount of data |
|
● as user data for input variables / as PROFINET IO controller / maximum |
8 Kibyte |
● as user data for input variables / as PROFINET IO controller / maximum |
8 Kibyte |
● as user data for input variables per PN IO device / as PROFINET IO controller / maximum |
1433 byte |
● as user data for output variables per PN IO device / as PROFINET IO controller / maximum |
1433 byte |
● as user data for input variables per PN IO device / for each sub-module as PROFINET IO controller / maximum |
256 byte |
● as user data for output variables per PN IO device / for each sub-module as PROFINET IO controller / maximum |
256 byte |
Performance data / telecontrol |
Protocol / is supported |
|
● TCP/IP |
Yes |
Product functions / management, configuration |
Product function / MIB support |
Yes |
Protocol / is supported |
|
● SNMP v1 |
Yes |
● DCP |
Yes |
● LLDP |
Yes |
Configuration software |
|
● required |
STEP 7 Professional V13 (TIA Portal) or higher |
Identification & maintenance function |
|
● I&M0 - device-specific information |
Yes |
● I&M1 – higher-level designation/location designation |
Yes |
Product functions / Diagnosis |
Product function / Web-based diagnostics |
Yes; yes, via S7-1500 CPU |
Product functions / switch |
Product feature / Switch |
Yes |
Product function |
|
● switch-managed |
No |
● with IRT / PROFINET IO switch |
Yes |
● Configuration with STEP 7 |
Yes |
Product functions / Redundancy |
Product function |
|
● Ring redundancy |
Yes |
● Redundancy manager |
Yes |
● Media Redundancy Protocol (MRP) |
Yes |
Product functions / Security |
Product function |
|
● switch-off of non-required services |
Yes |
● Blocking of communication via physical ports |
No |
● log file for unauthorized access |
No |
Product functions / Time |
Product function / SICLOCK support |
Yes |
Product function / pass on time synchronization |
Yes |
Protocol / is supported / NTP |
Yes |
Further Information / Internet Links |
Internet-Link |
|
● to website: Selector SIMATIC NET SELECTION TOOL |
http://www.siemens.com/snst |
● to website: Industrial communication |
http://www.siemens.com/simatic-net |
● to website: Information and Download Center |
http://www.siemens.com/automation/net/catalog |
● to website: Image database |
http://automation.siemens.com/bilddb |
● to website: CAx Download Manager |
http://www.siemens.com/cax |
● to website: Industry Online Support |
http://support.automation.siemens.com |
last modified: |
03.11.2014 |
Date 04.11.2014 |
Changes preserved © Copyright Siemens AG 2014 |