SIMATIC S7/PCS7, SM 322 DIGITAL OUTPUT MODULE, 16 DO, DC 24 V / 0,5A, CAPABLE OF DIAGNOSTICS, WIRE BREAK DETECTION TO 0 AND 1 SIGNAL, 1 X 40-PIN, INTERFACE MODULE IM 153-X HF NECESSARY |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
from load voltage L+ (without load), max. |
100 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power losses |
Power loss, typ. |
6 W |
Digital outputs |
Number of digital outputs |
16 |
Limitation of inductive shutdown voltage to |
L+ (-68 V) |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
4 kΩ |
Output voltage |
● for signal "1", min. |
L+ (-0.7 V) |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range, min. |
5 mA |
● for signal "1" permissible range, max. |
0.6 A |
● for signal "0" residual current, max. |
0.7 mA |
Switching frequency |
● with resistive load, max. |
100 Hz |
● on lamp load, max. |
10 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 60 °C, max. |
2 A |
vertical installation |
— up to 40 °C, max. |
2 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostics |
Yes |
● Wire break |
Yes |
● Short circuit |
Yes |
● Missing load voltage |
Yes |
Diagnostics indication LED |
● Rated load voltage PWR (green) |
No |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
4 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Connection method |
required front connector |
1x 40-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
350 g |
last modified: |
13.10.2014 |