SIMATIC S7-300, ANALOG INPUT SM 331, GALVANICALLY ISOLATED, 8 AI, 14 BIT, 0.052MS/CHANNEL, CURRENT, VOLTAGE, INTERRUPTS, DIAGNOSTICS,1 X 20 PIN, FIT FOR ISOCHRONE MODE IMPROVED DP-CYCLE TIME FOR ISOCHRONE MODE |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
50 mA |
from backplane bus 5 V DC, max. |
60 mA |
Power losses |
Power loss, typ. |
1.5 W |
Analog inputs |
Number of analog inputs |
8 |
permissible input voltage for voltage input (destruction limit), max. |
20 V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20) |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● 0 to +10 V |
No |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
100 kΩ |
● -1 V to +1 V |
Yes |
● Input resistance (-1 V to +1 V) |
10 MΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
100 kΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
100 kΩ |
● -500 mV to +500 mV |
Yes |
● -80 mV to +80 mV |
Yes |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
50 Ω |
● -20 to +20 mA |
Yes |
● Input resistance (-20 to +20 mA) |
50 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
50 Ω |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Measurement principle |
Actual value encryption |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
14 bit; Unipolar: 14 bits; bipolar: 13 bits + sign |
● Integration time, parameterizable |
Yes |
● Basic conversion time, ms |
52 µs per channel |
● Interference voltage suppression for interference frequency f1 in Hz |
none / 400 / 60 / 50 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
0.4 % |
● Current, relative to input area, (+/-) |
0.3 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.25 % |
● Current, relative to input area, (+/-) |
0.2 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
Yes |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable |
● Limit value alarm |
Yes; Parameterizable, channels 0 and 2 |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Diagnostics |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
200 g |
last modified: |
25.09.2014 |