SIMATIC DP, HART ANALOG INPUT SM 331, 8 AI, 0/4 - 20MA HART, FOR ET200M WITH IM153-2, 1 X 20-POLE, FEATURES: FW UPDATE, HART SECONDARY VARIABLES, REDUNDANCY, LOCAL DIAGNOSTIC BUFFER WITH TIMESTAMP, |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
20 mA |
from backplane bus 5 V DC, max. |
120 mA |
Output voltage |
Power supply to the transmitters |
● present |
Yes |
● Rated value (DC) |
24 V |
● short-circuit proof |
Yes |
Power losses |
Power loss, typ. |
1.5 W |
Analog inputs |
Number of analog inputs |
8 |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
No |
● Current |
Yes |
● Thermocouple |
No |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
240 Ω |
● Input resistance (-20 to +20 mA) |
240 Ω |
● Input resistance (4 to 20 mA) |
240 Ω |
Cable length |
● Cable length, shielded, max. |
800 m |
Analog value creation |
Measurement principle |
Sigma Delta |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
● Integration time, parameterizable |
Yes |
● Integration time, ms |
20 ms@50 Hz/16.6 ms@60 Hz/100 ms@100 Hz |
● Basic conversion time, including integration time, ms |
65ms@50Hz / 55ms@60Hz / 305ms@100Hz |
● Interference voltage suppression for interference frequency f1 in Hz |
60 / 50 / 10 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.01 % |
Temperature error (relative to input range), (+/-) |
0.001 %/K |
Crosstalk between the inputs, min. |
70 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.1 % |
Operational limit in overall temperature range |
● Current, relative to input area, (+/-) |
0.15 % |
Basic error limit (operational limit at 25 °C) |
● Current, relative to input area, (+/-) |
0.1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
40 dB |
● Common mode interference, min. |
100 dB |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
● Limit value alarm |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Diagnostics |
Yes |
● Group error |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels, in groups of |
8 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
117 mm |
Weights |
Weight, approx. |
205 g |