Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
28.8 V |
Input current |
from load voltage L+ (without load), max. |
20 mA |
from backplane bus 5 V DC, max. |
60 mA |
Power losses |
Power loss, typ. |
3 W |
Digital inputs |
Number of digital inputs |
8 |
Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 40 °C, max. |
16 |
— up to 60 °C, max. |
16 |
Input voltage |
● Rated value, DC |
24 V |
Input current |
● for signal "1", typ. |
6 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", min. |
1.2 ms |
— at "0" to "1", max. |
4.8 ms |
— at "1" to "0", min. |
1.2 ms |
— at "1" to "0", max. |
4.8 ms |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Digital outputs |
Number of digital outputs |
8 |
short-circuit protection |
Yes |
Controlling a digital input |
Yes |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Load resistance range |
● lower limit |
48 Ω |
● upper limit |
4 kΩ |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 60 °C, min. |
5 mA |
● for signal "1" permissible range for 0 to 60 °C, max. |
0.6 A |
● for signal "0" residual current, max. |
0.5 mA |
Output delay with resistive load |
● "0" to "1", max. |
350 µs |
● "1" to "0", max. |
500 µs |
Parallel switching of 2 outputs |
● for increased power |
No |
● for redundant control of a load |
Yes |
Switching frequency |
● with resistive load, max. |
100 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
10 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
4 A |
— up to 60 °C, max. |
3 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes |
— Permissible quiescent current (2-wire sensor), max. |
1.5 mA |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
● Alarms |
No |
Diagnostic messages |
● Diagnostic functions |
No |
Diagnostics indication LED |
● Status indicator digital output (green) |
Yes |
● Status indicator digital input (green) |
Yes |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Galvanic isolation digital outputs |
● between the channels |
No |
● between the channels and the backplane bus |
Yes |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
200 g |
last modified: |
16.09.2014 |