SIMATIC DP, HART ANALOG OUTPUT SM 332, 2AO, 0/4 - 20MA HART, FOR ET200M WITH IM153-2, 20 PIN |
|
Supply voltage |
Load voltage L+ |
Rated value (DC) |
24 V |
Reverse polarity protection |
Yes |
Input current |
from backplane bus 5 V DC, max. |
100 mA |
from supply voltage L+, max. |
150 mA |
Power losses |
Power loss, typ. |
3.5 W |
Analog outputs |
Number of analog outputs |
2 |
Voltage output, short-circuit protection |
Yes |
Current output, no-load voltage, max. |
19 V |
Cycle time (all channels) max. |
5 ms |
Output ranges, current |
0 to 20 mA |
Yes |
4 to 20 mA |
Yes |
Connection of actuators |
for current output two-wire connection |
Yes |
Load impedance (in rated range of output) |
with current outputs, max. |
650 Ω |
with current outputs, inductive load, max. |
7.5 mH |
Destruction limits against externally applied voltages and currents |
Voltages at the outputs towards MANA |
max. 17 V / -0.5 V |
Current, max. |
60 mA / -1 A |
Cable length |
Cable length, shielded, max. |
400 m |
Analog value creation |
Integrations and conversion time/resolution per channel |
Resolution with overrange (bit including sign), max. |
12 bit; Output value; 8 bit (+ sign) read back value |
Conversion time (per channel) |
40 ms |
Settling time |
for resistive load |
2.5 ms |
for capacitive load |
4 ms |
for inductive load |
2.5 ms |
Errors/accuracies |
Output ripple (based on output area, bandwidth 0 to 50 kHz), (+/-) |
0.02 % |
Linearity error (relative to output range), (+/-) |
0.03 % |
Temperature error (relative to output range), (+/-) |
0.01 %/K |
Crosstalk between the outputs, min. |
130 dB |
Repeat accuracy in steady state at 25 °C (relative to output area), (+/-) |
0.0050 % |
Operational limit in overall temperature range |
Current, relative to output area, (+/-) |
0.55 % |
Basic error limit (operational limit at 25 °C) |
Current, relative to output area, (+/-) |
0.15 % |
Interrupts/diagnostics/status information |
Substitute values connectable |
Yes; Parameterizable |
Alarms |
Diagnostic alarm |
Yes; Parameterizable |
Diagnostic messages |
Diagnostic functions |
Yes; Parameterizable |
Diagnostic information readable |
Yes |
Diagnostics |
Yes |
Overrange |
Yes |
Wire break |
Yes; as of output value > 0.5 mA |
Wire break in actuator cable |
Yes |
HART communication active |
Yes; green LED (H) |
Diagnostics indication LED |
Group error SF (red) |
Yes; Additional group message per channel |
Channel error indicator F (red) |
Yes; per channel |
Ex(i) characteristics |
Module for Ex(i) protection |
Yes |
Max. values of output circuits (per channel) |
Co (permissible external capacity), max. |
230 nF |
Io (short-circuit current), max. |
66 mA |
Lo (permissible external inductivity), max. |
7.5 mH |
Po (power of load), max. |
506 mW |
Uo (output no-load voltage), max. |
19 V |
Um (fault voltage), max. |
60 V; DC |
Ta (permissible ambient temperature), max. |
60 °C |
Galvanic isolation |
between the channels and backplane bus |
Yes |
Galvanic isolation analog outputs |
Galvanic isolation analog outputs |
Yes |
between the channels |
Yes |
between the channels and the load voltage L+ |
Yes |
Permissible potential difference |
between the outputs (UCM) |
60V DC/30V AC |
between M internally and the outputs |
60V DC/30V AC |
Isolation |
tested with |
Channels against backplane bus and load voltage L+ |
1500 V AC |
Channels among one another |
1500 V AC |
Load voltage L+ against backplane bus |
500 V DC |
Standards, approvals, certificates |
FM approval |
Available soon |
Use in hazardous areas |
Type of protection acc. to EN 50020 (CENELEC) |
[EEx ib] IIC |
Type of protection acc. to FM |
Class I, Division 2, Group A, B, C, D T4; Class I, Zone 2, Group IIC T4 |
Test number KEMA |
97 ATEX 2359 X |
Type of protection acc. to KEMA |
II3 (2) G Eex nA [ib] IIC T4 |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
280 g |
Status |
Jun 6, 2014 |