SIMATIC S7, DIGITAL INPUT SM 326, 8 DI; DC 24V, NAMUR, FAILSAFE NAMUR INPUTS FOR SIMATIC S7F SYSTEMS, UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/PLE (ISO13849), 1 X 40 PIN |
Supply voltage |
Rated value (DC) |
24 V |
Input current |
from load voltage L+ (without load), max. |
160 mA |
from backplane bus 5 V DC, max. |
90 mA |
Encoder supply |
Number of outputs |
8 |
Output voltage |
8.2 V DC |
Power loss |
Power loss, typ. |
4.5 W |
Digital inputs |
Number of digital inputs |
8; 8 (one-channel); 4 (two-channel) |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 40 °C, max. |
8; vertical setup |
— up to 60 °C, max. |
8; horizontal set up |
Input voltage |
● Type of input voltage |
DC |
● Rated value, DC |
in accordance with DIN 19234 or NAMUR |
Input current |
● for signal "0", max. (permissible quiescent current) |
0.35 to 1.2 mA |
● for signal "1", typ. |
2.1 to 7 mA |
Input delay (for rated value of input voltage) |
for NAMUR inputs |
— at "0" to "1", max. |
1.2 to 3 ms |
— at "1" to "0", max. |
1.2 to 3 ms |
Cable length |
● Cable length, shielded, max. |
200 m |
● Cable length unshielded, max. |
100 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic information readable |
Yes |
Diagnostics indication LED |
● Fail-safe operation |
Yes |
● Group error SF (red) |
Yes |
Ex(i) characteristics |
Module for Ex(i) protection |
Yes |
Maximum values of input circuits (per channel) |
● Co (permissible external capacity), max. |
3 µF |
● Io (short-circuit current), max. |
13.9 mA |
● Lo (permissible external inductivity), max. |
80 mH |
● Po (power of load), max. |
33.1 mW |
● Uo (output no-load voltage), max. |
10 V |
● Um (fault voltage), max. |
60V DC/30V AC |
● Ta (permissible ambient temperature), max. |
60 °C |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels |
Yes |
● between the channels and the backplane bus |
Yes |
● between the channels and the power supply of the electronics |
Yes |
Isolation |
Isolation tested with |
500 V DC |
tested with |
● Channels against backplane bus and load voltage L+ |
1500 V AC |
● Channels between each other |
1500 V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
● acc. to DIN VDE 0801 |
AK 4 (one channel), AK 5 und 6 (two channel) |
● acc. to EN 954 |
4 |
● acc. to IEC 61508 |
SIL 2 (single-channel), SIL 3 (two-channel) |
Use in hazardous areas |
● Test number KEMA |
99 ATEX 2671 X |
Connection method |
required front connector |
40-pin |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
482 g |
last modified: |
21.08.2014 |