SIMATIC S7, DIGITAL OUTPUT SM 326, 10 DO; 24V DC, 2A, FAILSAFE DIGITAL OUTPUT FOR SIMATIC S7F SYSTEMS WITH DIAGNOST. INTERRUPT, 1 X 40 PIN |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V; 1L+, 2L+, 3L+ |
Input current |
from load voltage1L+, max. |
70 mA; from supply voltage |
from load voltage 2L+ (without load), max. |
100 mA |
from load voltage 3L+ (without load), max. |
100 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power losses |
Power loss, typ. |
12 W |
Digital outputs |
Number of digital outputs |
10 |
short-circuit protection |
Yes |
Limitation of inductive shutdown voltage to |
L+ (-53 V) without series diode, L+ (-33 V) with series diode |
Switching capacity of the outputs |
● Lamp load, max. |
5 W |
Output voltage |
● for signal "1" with series diode, min. |
L+ (-1.8 V) |
● for signal "1" without series diode, min. |
L+ (-1 V) |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" permissible range for 0 to 40 °C, min. |
7 mA |
● for signal "1" permissible range for 0 to 40 °C, max. |
2 A; 2 A for horizontal installation, 1 A for vertical installation |
● for signal "1" permissible range for 40 to 60 °C, min. |
7 mA |
● for signal "1" permissible range for 40 to 60 °C, max. |
1 A; for horizontal installation |
● for signal "0" residual current, max. |
0.5 mA |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
2 Hz |
● on lamp load, max. |
10 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
7.5 A; without series diode, 5 A with series diode |
— up to 60 °C, max. |
5 A; without series diode, 4 A with series diode |
vertical installation |
— up to 40 °C, max. |
5 A; without series diode, 4 A with series diode |
Cable length |
● Cable length, shielded, max. |
1 000 m; 200 m for SIL3, AK 6, Cat 4 |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic information readable |
Yes |
Diagnostics indication LED |
● Fail-safe operation |
Yes |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels |
Yes |
● between the channels, in groups of |
5 |
● between the channels and the backplane bus |
Yes |
● between the channels and the power supply of the electronics |
Yes |
Isolation |
Isolation checked with |
500V DC/350V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
● acc. to DIN VDE 0801 |
AK 5 and 6 |
● acc. to EN 954 |
Cat. 4 |
● acc. to IEC 61508 |
SIL 3 |
Connection method |
required front connector |
40-pin |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
465 g |
last modified: |