SIMATIC S7-300, ANALOG INPUT SM 331, OPTICALLY ISOLATED, FOR EXPANDED TEMPERATURE RANGE, 2 AI, 9/12/14 BIT RESOLUTION, U/I/THERMOCOUPLE/RESISTANCE, INTERRUPT, DIAGNOSTICS, 20 PIN |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
80 mA |
from backplane bus 5 V DC, max. |
50 mA |
Power loss |
Power loss, typ. |
1.3 W |
Analog inputs |
Number of analog inputs |
2 |
Number of analog inputs for resistance measurement |
1 |
permissible input voltage for voltage input (destruction limit), max. |
20 V |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Voltage |
Yes |
● Current |
Yes |
● Thermocouple |
Yes |
● Resistance thermometer |
Yes |
● Resistance |
Yes |
Input ranges (rated values), voltages |
● 1 to 5 V |
Yes |
● Input resistance (1 to 5 V) |
100 kΩ |
● -1 V to +1 V |
Yes |
● Input resistance (-1 V to +1 V) |
10 MΩ |
● -10 V to +10 V |
Yes |
● Input resistance (-10 V to +10 V) |
100 kΩ |
● -2.5 V to +2.5 V |
Yes |
● Input resistance (-2.5 V to +2.5 V) |
100 kΩ |
● -250 mV to +250 mV |
Yes |
● Input resistance (-250 mV to +250 mV) |
10 MΩ |
● -5 V to +5 V |
Yes |
● Input resistance (-5 V to +5 V) |
100 kΩ |
● -500 mV to +500 mV |
Yes |
● Input resistance (-500 mV to +500 mV) |
10 MΩ |
● -80 mV to +80 mV |
Yes |
● Input resistance (-80 mV to +80 mV) |
10 MΩ |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
25 Ω |
● -10 to +10 mA |
Yes |
● Input resistance (-10 to +10 mA) |
25 Ω |
● -20 to +20 mA |
Yes |
● Input resistance (-20 to +20 mA) |
25 Ω |
● -3.2 to +3.2 mA |
Yes |
● Input resistance (-3.2 to +3.2 mA) |
25 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
25 Ω |
Input ranges (rated values), thermocouples |
● Type E |
Yes |
● Input resistance (Type E) |
10 MΩ |
● Type J |
Yes |
● Input resistance (type J) |
10 MΩ |
● Type K |
Yes |
● Input resistance (Type K) |
10 MΩ |
● Type N |
Yes |
● Input resistance (Type N) |
10 MΩ |
Input ranges (rated values), resistance thermometers |
● Ni 100 |
Yes; Standard |
● Pt 100 |
Yes; Standard |
● Input resistance (Pt 100) |
10 MΩ |
Input ranges (rated values), resistors |
● 0 to 150 Ohm |
Yes |
● Input resistance (0 to 150 Ohm) |
10 MΩ |
● 0 to 300 Ohm |
Yes |
● Input resistance (0 to 300 Ohm) |
10 MΩ |
● 0 to 600 Ohm |
Yes |
● Input resistance (0 to 600 Ohm) |
10 MΩ |
Thermocouple (TC) |
Temperature compensation |
— parameterizable |
Yes |
— internal temperature compensation |
Yes |
— external temperature compensation with compensations socket |
Yes |
Characteristic linearization |
● parameterizable |
Yes |
— for thermocouples |
Type E, J, K, N |
— for resistance thermometer |
Pt100 (standard), Ni100 (standard) |
Cable length |
● Cable length, shielded, max. |
200 m; 50 m at 80 mV |
Analog value generation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
15 bit; Unipolar: 9/12/12/14 bits; bipolar: 9 bits + sign/12 bits + sign/12 bits + sign/14 bits + sign |
● Integration time, ms |
2,5 / 16,67 / 20 / 100 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 / 10 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
● for resistance measurement with two-wire connection |
Yes |
● for resistance measurement with three-wire connection |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Operational error limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
1 % |
● Current, relative to input area, (+/-) |
1 % |
● Resistance, relative to input area, (+/-) |
1 % |
● Resistance thermometer, relative to input area, (+/-) |
1 % |
Basic error limit (operational limit at 25 °C) |
● Voltage, relative to input area, (+/-) |
0.6 % |
● Current, relative to input area, (+/-) |
0.6 % |
● Resistance, relative to input area, (+/-) |
0.6 % |
● Resistance thermometer, relative to input area, (+/-) |
0.6 % |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Channel 0 |
● Limit value alarm |
Yes |
Diagnostic messages |
● Diagnostics |
Yes; Diagnostic information readable |
● Group error |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation tested with |
500 V DC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
250 g |
last modified: |
21.08.2014 |