Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● permissible range, lower limit (DC) |
20.4 V |
● permissible range, upper limit (DC) |
57.6 V |
Input current |
from load voltage L+ (without load), max. |
200 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power losses |
Power loss, typ. |
2.8 W |
Digital outputs |
Number of digital outputs |
16 |
Switching capacity of the outputs |
● Lamp load, max. |
2.5 W |
Output current |
● for signal "1" rated value |
0.5 A |
● for signal "1" permissible range for 0 to 40 °C, max. |
0.5 A |
● for signal "1" permissible surge current, max. |
1.5 A |
● for signal "0" residual current, max. |
10 µA |
Switching frequency |
● with resistive load, max. |
10 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
0.5 Hz |
Aggregate current of outputs (per group) |
horizontal installation |
— up to 40 °C, max. |
0.5 A |
— up to 60 °C, max. |
0.5 A |
vertical installation |
— up to 40 °C, max. |
0.5 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostics |
Yes |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
1 |
● between the channels and the backplane bus |
Yes |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
260 g |
last modified: |
16.09.2014 |