Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from backplane bus 5 V DC, max. |
100 mA |
from supply voltage L+, max. |
180 mA |
Output voltage |
Power supply to the transmitters |
● present |
Yes |
● Rated value (DC) |
15 V |
● short-circuit proof |
Yes |
● No-load voltage (DC) |
29.6 V |
Power losses |
Power loss, typ. |
4.5 W |
Analog inputs |
Number of analog inputs |
2 |
permissible input current for current input (destruction limit), max. |
40 mA |
Input ranges |
● Current |
Yes |
Input ranges (rated values), currents |
● 0 to 20 mA |
Yes |
● Input resistance (0 to 20 mA) |
50 Ω |
● 4 to 20 mA |
Yes |
● Input resistance (4 to 20 mA) |
50 Ω |
Cable length |
● Cable length, shielded, max. |
400 m |
Analog value creation |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit |
● Integration time, parameterizable |
Yes |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies |
Linearity error (relative to input range), (+/-) |
0.01 % |
Temperature error (relative to input range), (+/-) |
0.01 %/K |
Crosstalk between the inputs, min. |
130 dB |
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) |
0.05 % |
Operational limit in overall temperature range |
● Current, relative to input area, (+/-) |
0.45 % |
Basic error limit (operational limit at 25 °C) |
● Current, relative to input area, (+/-) |
0.1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
60 dB |
● Common mode interference, min. |
130 dB |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
● Limit value alarm |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Overrange |
Yes |
● Wire break in signal transmitter cable |
Yes |
● Short circuit of the signal encoder cable |
Yes |
● HART communication active |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
● Channel error indicator F (red) |
Yes |
Ex(i) characteristics |
Module for Ex(i) protection |
Yes |
Max. values of input circuits (per channel) |
● Co (permissible external capacity), max. |
62 nF |
● Io (short-circuit current), max. |
96.1 mA |
● Lo (permissible external inductivity), max. |
3 mH |
● Po (power of load), max. |
511 mW |
● Uo (output no-load voltage), max. |
26 V |
● Um (fault voltage), max. |
250 V |
● Ta (permissible ambient temperature), max. |
0.6 °C |
Galvanic isolation |
between the channels and backplane bus |
Yes |
Galvanic isolation analog inputs |
● Galvanic isolation analog inputs |
Yes |
Galvanic isolation analog outputs |
● between the channels |
Yes |
● between the channels and the load voltage L+ |
Yes |
Ambient conditions |
Operating temperature |
● max. |
60 °C |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
260 g |
last modified: |