SIMATIC S7, DIGITAL INPUT SM 326, F-DI 24 X DC 24V, FAILSAFE DIGITAL INPUTS FOR SIMATIC S7 FAILSAFE SYSTEMS WITH DIAGNOST. INTERRUPT, UP TO CATEGORY 4 (EN954-1)/ SIL3 (IEC61508)/PLE (ISO13849), 1 X 40 PIN |
Supply voltage |
Rated value (DC) |
24 V |
Input current |
from load voltage L+ (without load), max. |
450 mA |
from backplane bus 5 V DC, max. |
100 mA |
Encoder supply |
Number of outputs |
4; Isolated |
Output current |
● Rated value |
400 mA |
Power losses |
Power loss, typ. |
10 W |
Digital inputs |
Number of digital inputs |
24 |
Number of simultaneously controllable inputs |
all mounting positions |
— up to 40 °C, max. |
24 |
— up to 60 °C, max. |
24; (at 24 V) or 18 (at 28.8 V) |
Input voltage |
● Type of input voltage |
DC |
● Rated value, DC |
24 V |
● for signal "0" |
-30 to +5 V |
● for signal "1" |
+11 to +30 V |
Input current |
● for signal "0", max. (permissible quiescent current) |
2 mA |
● for signal "1", typ. |
10 mA |
Input delay (for rated value of input voltage) |
for standard inputs |
— at "0" to "1", max. |
3.4 ms |
— at "1" to "0", max. |
3.4 ms |
Cable length |
● Cable length, shielded, max. |
200 m |
● Cable length unshielded, max. |
100 m |
Encoder |
Connectable encoders |
● 2-wire sensor |
Yes; if short-circuit test is deactivated |
— Permissible quiescent current (2-wire sensor), max. |
2 mA |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
Diagnostics indication LED |
● Fail-safe operation |
Yes |
● Group error SF (red) |
Yes |
Ex(i) characteristics |
Max. values of input circuits (per channel) |
● Ta (permissible ambient temperature), max. |
60 °C |
Galvanic isolation |
Galvanic isolation digital inputs |
● between the channels |
Yes |
● between the channels, in groups of |
12 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500V DC/350V AC |
Standards, approvals, certificates |
Highest safety class achievable in safety mode |
● acc. to DIN VDE 0801 |
AK 6 |
● acc. to EN 954 |
Cat. 4 |
● acc. to IEC 61508 |
SIL 3 |
Connection method |
required front connector |
40-pin |
Dimensions |
Width |
80 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
442 g |
last modified: |