SIMATIC S7-300, ANALOG INPUT SM 331, INDIVIDUALLY ISOLATATED AC250V, 6 AI THERMOCOUPLE, TYPE B, E, J, K, L, N, R, S, T VOLTAGE: +/-25MV BIS +/-1V 16 BIT, 50 MS, 1 X 40 PIN |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
150 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power losses |
Power loss, typ. |
2.2 W |
Analog inputs |
Number of analog inputs |
6 |
permissible input voltage for voltage input (destruction limit), max. |
35 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
Input ranges |
● Voltage |
Yes |
● Current |
No |
● Thermocouple |
Yes |
● Resistance thermometer |
No |
● Resistance |
No |
Input ranges (rated values), voltages |
● 0 to +10 V |
No |
● 1 to 5 V |
No |
● 1 to 10 V |
No |
● -1 V to +1 V |
Yes |
● Input resistance (-1 V to +1 V) |
10 MΩ |
● -10 V to +10 V |
No |
● -2.5 V to +2.5 V |
No |
● -250 mV to +250 mV |
Yes |
● Input resistance (-250 mV to +250 mV) |
10 MΩ |
● -5 V to +5 V |
No |
● -50 mV to +50 mV |
Yes |
● Input resistance (-50 mV to +50 mV) |
10 MΩ |
● -500 mV to +500 mV |
Yes |
● Input resistance (-500 mV to +500 mV) |
10 MΩ |
● -80 mV to +80 mV |
Yes |
● Input resistance (-80 mV to +80 mV) |
10 MΩ |
Input ranges (rated values), currents |
● 0 to 20 mA |
No |
● -10 to +10 mA |
No |
● -20 to +20 mA |
No |
● -3.2 to +3.2 mA |
No |
● 4 to 20 mA |
No |
Input ranges (rated values), thermoelements |
● Type B |
Yes |
● Input resistance (Type B) |
10 MΩ |
● Type E |
Yes |
● Input resistance (Type E) |
10 MΩ |
● Type J |
Yes |
● Input resistance (type J) |
10 MΩ |
● Type K |
Yes |
● Input resistance (Type K) |
10 MΩ |
● Type L |
Yes |
● Input resistance (Type L) |
10 MΩ |
● Type N |
Yes |
● Input resistance (Type N) |
10 MΩ |
● Type R |
Yes |
● Input resistance (Type R) |
10 MΩ |
● Type S |
Yes |
● Input resistance (Type S) |
10 MΩ |
● Type T |
Yes |
● Input resistance (Type T) |
10 MΩ |
● Type U |
Yes |
● Input resistance (Type U) |
10 MΩ |
● Type TXK/TXK(L) to GOST |
Yes |
● Input resistance (Type TXK/TXK(L) to GOST) |
10 MΩ |
Input ranges (rated values), resistance thermometer |
● Cu 10 |
No |
● Ni 100 |
No |
● Ni 1000 |
No |
● LG-Ni 1000 |
No |
● Ni 120 |
No |
● Ni 200 |
No |
● Ni 500 |
No |
● Pt 100 |
No |
● Pt 1000 |
No |
● Pt 200 |
No |
● Pt 500 |
No |
Input ranges (rated values), resistors |
● 0 to 150 ohms |
No |
● 0 to 300 ohms |
No |
● 0 to 600 ohms |
No |
● 0 to 6000 ohms |
No |
Thermocouple (TC) |
Temperature compensation |
— Parameterizable |
Yes |
— internal temperature compensation |
Yes |
— external temperature compensation with compensations socket |
Yes |
— external temperature compensation with Pt100 |
Yes |
Characteristic linearization |
● Parameterizable |
Yes |
— for thermocouples |
Type B, E, J, K, L, N, R, S. T, U, C, TXK, XK(L) |
— for resistance thermometer |
No |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; Two''s complement |
● Integration time, parameterizable |
Yes |
● Basic conversion time, ms |
30 / 50 / 60 / 300 |
● Integration time, ms |
10 / 16,67 / 20 / 100 |
● Interference voltage suppression for interference frequency f1 in Hz |
10 / 50 / 60 / 400 Hz |
Errors/accuracies |
Operational limit in overall temperature range |
● Voltage, relative to input area, (+/-) |
1 % |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; channel by channel |
● Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostic functions |
Yes; Parameterizable |
● Diagnostic information readable |
Yes |
● Diagnostics |
Yes |
● Group error |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
Yes |
● between the channels, in groups of |
1 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
2500 V DC |
Connection method |
required front connector |
40-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
272 g |
last modified: |