SIMATIC S7-300, ANALOG INPUT SM 331, OPT. ISOL.,2/3/4 WIRE, 8AI, RESISTANCE, PT100/200/1000 NI100/120/200/500/1000, CU10, PLUS CHARACTERISTICS ACCORDING TO GOST STANDARD 16 (INTERN 24) BIT, 50MS, 1 X 40 PIN |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
240 mA |
from backplane bus 5 V DC, max. |
100 mA |
Power losses |
Power loss, typ. |
4.6 W |
Analog inputs |
Number of analog inputs |
8 |
Number of analog inputs for resistance measurement |
8 |
permissible input voltage for voltage input (destruction limit), max. |
75 V; 35 V continuous, 75 V for max. 1 s (mark to space ratio 1:20) |
Input ranges |
● Voltage |
No |
● Current |
No |
● Thermocouple |
No |
● Resistance thermometer |
Yes |
● Resistance |
Yes |
Input ranges (rated values), voltages |
● 0 to +10 V |
No |
● 1 to 5 V |
No |
● 1 to 10 V |
No |
● -1 V to +1 V |
No |
● -10 V to +10 V |
No |
● -2.5 V to +2.5 V |
No |
● -250 mV to +250 mV |
No |
● -5 V to +5 V |
No |
● -50 mV to +50 mV |
No |
● -500 mV to +500 mV |
No |
● -80 mV to +80 mV |
No |
Input ranges (rated values), currents |
● 0 to 20 mA |
No |
● -10 to +10 mA |
No |
● -20 to +20 mA |
No |
● -3.2 to +3.2 mA |
No |
● 4 to 20 mA |
No |
Input ranges (rated values), thermoelements |
● Type B |
No |
● Type E |
No |
● Type J |
No |
● Type K |
No |
● Type L |
No |
● Type N |
No |
● Type R |
No |
● Type S |
No |
● Type T |
No |
● Type U |
No |
● Type TXK/TXK(L) to GOST |
No |
Input ranges (rated values), resistance thermometer |
● Cu 10 |
Yes |
● Ni 100 |
Yes |
● Ni 1000 |
Yes |
● LG-Ni 1000 |
Yes |
● Ni 120 |
Yes |
● Ni 200 |
Yes |
● Ni 500 |
Yes |
● Pt 100 |
Yes |
● Pt 1000 |
Yes |
● Pt 200 |
Yes |
● Pt 500 |
Yes |
Input ranges (rated values), resistors |
● 0 to 150 ohms |
Yes |
● 0 to 300 ohms |
Yes |
● 0 to 600 ohms |
Yes |
Characteristic linearization |
● Parameterizable |
Yes |
— for resistance thermometer |
Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni200, Ni500, Ni1000, Cu10; (standard/climate) |
Cable length |
● Cable length, shielded, max. |
200 m |
Analog value creation |
Measurement principle |
integrating |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; Two''s complement |
● Integration time, parameterizable |
Yes |
● Basic conversion time, ms |
up to 4 channels: 10 ms per module, over 5 channels: 190 ms per module, 8 channels: 80 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 Hz |
Encoder |
Connection of signal encoders |
● for resistance measurement with two-wire connection |
Yes; without resistance correction |
● for resistance measurement with three-wire connection |
Yes |
● for resistance measurement with four-wire connection |
Yes |
Errors/accuracies |
Operational limit in overall temperature range |
● Resistance, relative to input area, (+/-) |
0.1 % |
● Resistance thermometer, relative to input area, (+/-) |
+/- 1 K |
Basic error limit (operational limit at 25 °C) |
● Resistance, relative to input area, (+/-) |
0.05 % |
● Resistance thermometer, relative to input area, (+/-) |
+/- 0,5 K |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
Yes; Parameterizable per group |
● Limit value alarm |
Yes; Parameterizable |
Diagnostic messages |
● Diagnostic functions |
Yes; Parameterizable |
● Diagnostic information readable |
Yes |
● Diagnostics |
Yes |
Diagnostics indication LED |
● Group error SF (red) |
Yes |
Galvanic isolation |
Galvanic isolation analog inputs |
● between the channels |
No |
● between the channels, in groups of |
2 |
● between the channels and the backplane bus |
Yes |
Isolation |
Isolation checked with |
500 V DC |
Connection method |
required front connector |
40-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
272 g |
last modified: |
25.09.2014 |