SIMATIC S7, ANALOG INPUT SM 331, OPTICALLY ISOLATATED, 8 AI THERMOCOUPLE/4 AI PT100, F. SIGNALS F. HAZARDOUS AREAS, CAPABLE OF DIAGNOST.,PTB-TESTED 1 X 20 PIN |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
Input current |
from backplane bus 5 V DC, max. |
120 mA |
Power loss |
Power loss, typ. |
0.6 W |
Analog inputs |
Number of analog inputs |
8; 8x thermocouples; 4x RTD thermoresistors |
Input ranges |
● Thermocouple |
Yes |
● Resistance thermometer |
Yes |
Input ranges (rated values), thermocouples |
● Type B |
Yes |
● Input resistance (Type B) |
10 MΩ |
● Type E |
Yes |
● Input resistance (Type E) |
10 MΩ |
● Type J |
Yes |
● Input resistance (type J) |
10 MΩ |
● Type K |
Yes |
● Input resistance (Type K) |
10 MΩ |
● Type L |
Yes |
● Input resistance (Type L) |
10 MΩ |
● Type N |
Yes |
● Input resistance (Type N) |
10 MΩ |
● Type R |
Yes |
● Input resistance (Type R) |
10 MΩ |
● Type S |
Yes |
● Input resistance (Type S) |
10 MΩ |
● Type T |
Yes |
● Input resistance (Type T) |
10 MΩ |
● Type U |
Yes |
● Input resistance (Type U) |
10 MΩ |
Input ranges (rated values), resistance thermometers |
● Ni 100 |
Yes |
● Input resistance (Ni 100) |
10 MΩ |
● Pt 100 |
Yes |
● Input resistance (Pt 100) |
10 MΩ |
● Pt 200 |
Yes |
● Input resistance (Pt 200) |
10 MΩ |
Cable length |
● Cable length, shielded, max. |
200 m; TC: 50 m |
Analog value generation |
Measurement principle |
Sigma Delta |
Integration and conversion time/resolution per channel |
● Resolution with overrange (bit including sign), max. |
16 bit; 10 to 15 bits + sign |
● Integration time, parameterizable |
Yes; 2.5 to 100 ms |
● Interference voltage suppression for interference frequency f1 in Hz |
10 to 400 Hz |
Encoder |
Connection of signal encoders |
● for current measurement as 2-wire transducer |
Yes |
● for current measurement as 4-wire transducer |
Yes |
Errors/accuracies |
Temperature error (relative to input range), (+/-) |
Temperature error: 0.001 to 0.002 %/K |
Operational error limit in overall temperature range |
● Resistance thermometer, relative to input area, (+/-) |
0.09 to 0.04% |
Basic error limit (operational limit at 25 °C) |
● Resistance thermometer, relative to input area, (+/-) |
0.1 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
● Series mode interference (peak value of interference < rated value of input range), min. |
60 dB |
● Common mode interference, min. |
130 dB |
Interrupts/diagnostics/status information |
Diagnostic messages |
● Diagnostic functions |
Yes |
● Diagnostic information readable |
Yes |
● Overrange |
Yes |
● Wire-break in signal transmitter cable |
Yes |
● Short-circuit of the signal encoder cable |
Yes |
Diagnostics indication LED |
● Short-circuit per channel (red) |
Yes |
● Short-circuit group error (red) |
Yes |
Ex(i) characteristics |
Module for Ex(i) protection |
Yes |
Maximum values of input circuits (per channel) |
● Co (permissible external capacity), max. |
43 µF |
● Io (short-circuit current), max. |
28.8 mA |
● Lo (permissible external inductivity), max. |
40 mH |
● Po (power of load), max. |
41.4 mW |
● Uo (output no-load voltage), max. |
5.9 V |
Galvanic isolation |
Galvanic isolation analog inputs |
● Galvanic isolation analog inputs |
Yes |
Permissible potential difference |
between the inputs (UCM) |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
between inputs and MANA (UCM) |
60 V DC/30 V AC when used in the hazardous area; 400 V DC/250 V AC when used in NON-hazardous area |
Standards, approvals, certificates |
Use in hazardous areas |
● Type of protection acc. to EN 50020 (CENELEC) |
[EEx ib] IIC |
● Type of protection acc. to FM |
Class I, Division 2, Group A, B, C, D T4 |
● Test number PTB |
Ex-96.D.2108X |
Ambient conditions |
Operating temperature |
● max. |
60 °C |
Connection method |
required front connector |
20-pin |
Weights |
Weight, approx. |
210 g |
last modified: |
21.08.2014 |