SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED, 8 DO (RELAY), 1 X 20 PIN, 24V DC, 2A OR 230V AC, 2A |
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V |
Input current |
from load voltage L+ (without load), max. |
110 mA; Current consumption of relay |
from load voltage L1 (without load), max. |
110 mA |
from backplane bus 5 V DC, max. |
40 mA |
Power losses |
Power loss, typ. |
3.2 W |
Digital outputs |
Number of digital outputs |
8; Relays |
Switching capacity of the outputs |
● Lamp load, max. |
50 W |
Output current |
● for signal "1" rated value |
2 A |
● for signal "1" minimum load current |
5 mA |
Switching frequency |
● with resistive load, max. |
2 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
2 Hz |
● mechanical, max. |
10 Hz |
Relay outputs |
● Rated input voltage of relay coil L+ (DC) |
24 V; 110 mA |
● Number of operating cycles, max. |
300 000; 230 V AC: 100000; 120 V AC: 200000; 24 V DC: 300000 (at 2 A) |
Switching capacity of contacts |
— with inductive load, max. |
2 A; 2 A (230 V AC), 2 A (24 V DC) |
— with resistive load, max. |
2 A |
Cable length |
● Cable length, shielded, max. |
1 000 m |
● Cable length unshielded, max. |
600 m |
Interrupts/diagnostics/status information |
Alarms |
● Diagnostic alarm |
No |
Diagnostic messages |
● Diagnostics |
No |
● Wire break |
No |
● Short circuit |
No |
● Fuse blown |
No |
● Missing load voltage |
No |
Diagnostics indication LED |
● Rated load voltage PWR (green) |
No |
● Fuse OK FSG (green) |
No |
Galvanic isolation |
Galvanic isolation digital outputs |
● between the channels, in groups of |
2 |
● between the channels and the backplane bus |
Yes; Optocoupler |
Isolation |
Isolation checked with |
1500 V AC |
Connection method |
required front connector |
20-pin |
Dimensions |
Width |
40 mm |
Height |
125 mm |
Depth |
120 mm |
Weights |
Weight, approx. |
190 g |
last modified: |